Fluke 724 Fluke 724 Users Manual - Page 42
Calibrating a Transmitter, keys. Enter these parameters by pressing
View all Fluke 724 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 42 highlights
724 Users Manual Calibrating a Transmitter Use the measurement (upper display) and source (lower display) modes to calibrate a transmitter. The following example shows how to calibrate a temperature transmitter. Connect the calibrator to the instrument under test as shown in Figure 15. Proceed as follows to calibrate a transmitter: 1. Press K for current measurement with loop power. 2. Press T (lower display). If desired, continue pressing this key to select the desired thermocouple type. M 3. If necessary, press for SOURCE mode. 4. Set your zero and span parameters by pressing X and W keys. Enter these parameters by pressing and holding J and G. For more information on setting parameters, see "Setting 0 % and 100 %" earlier in this manual. 5. Perform test checks at 0-25-50-75-100 % points by pressing H or I. Adjust the transmitter as necessary. 32