Circuit Breaker Installation and Wiring Circuit breakers are to be supplied by the installer. Refer to the circuit breaker chart below for a list of suitable circuit breakers that can be used. Follow the code and the circuit breaker manufacturer's rating requirements regarding the size and temperature rating for wiring. Note that some pool equipment may be required to be connected to ground fault circuit breakers-check local and NEC (CEC) codes. Manufacturer Siemens SUITABLE LISTED BREAKERS Tightening Single Double Twin Quad GFCB Filler Plates Torque QP QP QT QT QPF QF3 25lb-in Murray MP-T MP-T MH-T MH-T MP-GT LX100FP 25lb-in General Purpose Outlet If desired, a duplex receptacle with weatherproof cover (supplied by installer) may be installed in the knockouts on the lower right side of the ECOMMAND 4 enclosure. Per code, the receptacle should be a GFCI type. Alternatively, connect a standard receptacle to a GFCB. ECOMMAND 4 Control Power The ECOMMAND 4 requires 120VAC, 2A power to operate the control logic circuits. This power should be connected to a circuit breaker rated at 125% of the intended load or the next higher size available. 120, 2VA Factory Prewired Field Wired 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

Circuit Breaker Installation and Wiring
Circuit breakers are to be supplied by the installer.
Refer to the circuit breaker chart below for a list of
suitable circuit breakers that can be used.
Follow the code and the circuit breaker manufacturer’s rating
requirements regarding the size and temperature rating for wiring.
Note that some pool equipment may be
required to be connected to ground fault circuit breakers—check local and NEC (CEC) codes.
General Purpose Outlet
If desired, a duplex receptacle with weatherproof cover (supplied by installer) may be installed in the
knockouts on the lower right side of the ECOMMAND 4 enclosure.
Per code, the receptacle should be
a GFCI type.
Alternatively, connect a standard receptacle to a GFCB.
ECOMMAND 4 Control Power
The ECOMMAND 4 requires 120VAC, 2A
power to operate the control logic circuits.
This power
should be connected to a circuit breaker rated at 125% of the intended load or the next higher size
available.
6
Siemens
Murray
Manufacturer
Single Double
Quad
Twin
GFCB
Filler Plates
QP
QP
QT
QT
QPF
QF3
SUITABLE LISTED BREAKERS
Tightening
Torque
MP-T
MP-T
MH-T
MH-T
MP-GT
LX100FP
25lb-in
25lb-in
Factory
Prewired
Field
Wired
120, 2VA