HP 200 HP StorageWorks 200 Storage Virtualization System site preparation guid
HP 200 Manual
View all HP 200 manuals
Add to My Manuals
Save this manual to your list of manuals |
HP 200 manual content summary:
- HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 1
HP StorageWorks 200 Storage Virtualization System site preparation guide This guide describes how to prepare your site for the HP StorageWorks 200 Storage Virtualization System. Part number: AE071-96003 Second edition: October 2006 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 2
. Confidential computer software. Valid license from HP required for possession, use or copying. Consistent HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 3
this guide 5 Intended audience 5 System 5 Related Documentation 5 Document conventions and symbols 6 Rack stability 7 HP technical support 7 Subscription service 7 HP web requirements 32 Electrical requirements 33 HP StorageWorks 200 Storage Virtualization System site preparation guide 3 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 4
Line voltage 33 Branch circuit breakers 33 Single-phase branch circuit breakers 33 Frequency 33 Safety and dedicated earth ground 33 Grounding requirements 33 AC connections 34 Power line transients 34 Protection against sources of electrical interference 34 Uninterruptible power supply ( - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 5
System configuration guide You can find these documents from the Manuals page of the HP Business Support Center web site: http://www.hp.com/support/manuals. In the Storage section, click Storage array systems and then select your product. HP StorageWorks 200 Storage Virtualization System site - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 6
text: Document conventions and symbols Blue, underlined text: http://www.hp.com Bold text Italic text Monospace text Monospace, italic text Monospace data. IMPORTANT: Provides clarifying information or specific instructions. NOTE: Provides additional information. TIP: Provides helpful hints and - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 7
driver versions, and firmware documentation updates as well as instant access to numerous other product resources. After subscribing, locate your products by selecting Business support and then Storage under Product Category. HP StorageWorks 200 Storage Virtualization System site preparation guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 8
sites For additional information, see the following HP web sites: • http://www.hp.com • http://www.hp.com/go/storage • http://www.hp.com/service_locator • http://www.hp.com/support/manuals • http://www.hp.com/support/downloads Documentation feedback HP welcomes your feedback. To make comments and - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 9
The HP service organization is committed to making sure you receive maximum benefit from your system. HP representatives will guide and assist you via phone consultation throughout the site prep process and will assist you on site with installation. HP StorageWorks 200 Storage Virtualization System - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 10
. 2. Carefully review Chapter 2 to understand the site requirements for the system. As you prepare to install the HP SVS200, be sure to take the requirements of connected storage systems into account. See the documentation for the storage system. 3. Use the information, instructions, and tools - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 11
include the new system? Does the new floor plan include adequate space for airflow and servicing needs? Does the new floor plan include the clearance required for the floor's load rating? specifications Humidity specifications HP StorageWorks 200 Storage Virtualization System site preparation guide 11 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 12
an escort)? Does the computer room have access control (for example, do HP representatives need a security code)? Are all floors, stairs, elevators, stairwalkers, lifts, ramps, or ladders needed to move the equipment adequate to support its weight and size? Will the equipment fit through all doors and - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 13
building alterations • Placing an order for data comm equipment The time between placing an equipment order and actual delivery can vary. Contact your HP representative to determine the best estimated delivery dates. HP StorageWorks 200 Storage Virtualization System site preparation guide 13 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 14
14 Site prep team and tasks - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 15
• Safety requirements • Raised floor requirements • Environmental requirements • Data comm requirements • Electrical requirements • Protection against sources of electrical interference • Uninterruptible power supply (UPS) HP StorageWorks 200 Storage Virtualization System site preparation guide 15 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 16
Front view HP SVS200 Controller Service Processor PC (SVP) Space where a second factory-installed SVS200 Controller resides if you ordered a second unit with this rack. Contains buttons and switches for operating the SVS200. Refer to the HP StorageWorks 200 Storage Virtualization System owner's guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 17
mm, 24.0 inches 950 mm, 37.4 inches Depth 925 mm, 36.4 inches 1110 mm, 43.7 inches Height 1920 mm, 75.6 inches 2030 mm, 79.9 inches HP StorageWorks 200 Storage Virtualization System site preparation guide 17 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 18
later. The second table shows the maximums if you add a second HP SVS200 Controller with all options in the same rack. Packaging for delivery maximum values if all available options are added) 24/54 0.7 0.7 Second HP SVS200 Controller 1-127+ TB Bundle (maximum) 101/222 1.2 1.2 Second Set - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 19
or doors. CAUTION: Make sure all floors, stairs, and elevators you use when moving the system to the computer room can support the weight and size of the equipment. Failure to do so could damage the equipment or your site. HP StorageWorks 200 Storage Virtualization System site preparation guide 19 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 20
codes for a data center/computer room environment. HP recommends that you follow these general guidelines: component damage, especially during servicing operations. Static charges be generated when two objects are separated. For example, printer paper is often stored in cool dry conditions. If - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 21
create a safety hazard. Electrical hazards The system equipment racks contain dangerous voltages. To prevent injury or death from electric shock, refer all electrical installation and service to qualified personnel. HP StorageWorks 200 Storage Virtualization System site preparation guide 21 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 22
and other equipment and furniture • Provides clearance around the system for service access and to ensure proper weight distribution on the computer room's and by phone with your HP representative. Raised floor requirements The computer room floor must be able to support the total weight of the - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 23
: HP strongly discourages the use of carpeting, including antistatic varieties, within 6.0 m (20 ft.) of the system. Over time, carpeting may shed dust that can cause problems with equipment damage through static discharge. HP StorageWorks 200 Storage Virtualization System site preparation guide 23 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 24
and cutout dimensions Figures on the following pages show the clearance dimensions, locations of floor cutouts, and other dimensions for the SVS200 rack. NOTE: The HP SVS200 includes a cabling hole with sliding cover in the top of the rack for cable drops from the ceiling. The hole is located in the - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 25
. Never use this space for storage. • Additional space required to properly distribute the equipment weight on your computer room's raised floor. The amount of additional space required depends on your floor load rating. HP StorageWorks 200 Storage Virtualization System site preparation guide 25 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 26
as a desk or wall. • Clearance "b" is the space between the service clearance at the right side of the system (100 mm for the kickplate) and any value from the table is 600 mm, then "a" can be 400 mm and "b" can be 200, or both "a" and "b" can be 300. 4. Calculate clearances by filling in and - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 27
multiple systems are arranged in a row, base your clearance values on the requirements of the largest system. • Generally, clearances ("c") should be as large as allowable. HP StorageWorks 200 Storage Virtualization System site preparation guide 27 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 28
for operating this system must be satisfied before installation. Altitude The maximum altitude for system operation is 3,000 meters. For nonoperational or storage situations, the maximum altitude is 4,000 meters. Air conditioning Use separate computer room air conditioning duct work. If it is not - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 29
(ESD) voltage potential. ESD can cause component damage during servicing operations. Low humidity levels are often the result of the degrees F Shipping and storage maximum wet bulb temperature 29 degrees C 84 degrees F HP StorageWorks 200 Storage Virtualization System site preparation guide 29 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 30
mm, 5-10 Hz 0.5 G, 10-70 Hz 0.05 mm, 70-99 Hz 1.0 G, 99-300 Hz Shipping and storage (product packed in factory packing) 0.5 G, 15 minutes (at four most severe resonances between 5-200 Hz) Shock specifications The following table lists shock specifications. For horizontal shock testing methods, see - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 31
cleaners, or printer component wear. tiles. Although this problem is relatively rare, HP strongly recommends that your site be evaluated for metallic particulate contamination before installation of electronic equipment. HP StorageWorks 200 Storage Virtualization System site preparation guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 32
representative will configure Continuous Track XP. For more information on Continuous Track XP, see the owner's guide. A twisted pair (Cat 5) cableAn Needed to connect the HP system to an available Ethernet port on your available LAN drop on your LAN. To ensure network security, consult with your - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 33
support at the service equipment or other HP system requires a solidly conductor-connected ground and may require a separate neutral in the case of WYE or STAR connections. For the HP system, TN grounding systems are preferred. HP StorageWorks 200 Storage Virtualization System site preparation guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 34
the cords and plugs you need when you order the HP 200 Storage Virtualization System. You are responsible for having the correct plugs and the same neutral/ground for more than one circuit causes voltage loss and heat problems and can create a fire hazard. A shared neutral conductor that fails open- - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 35
you use for the storage it controls. CAUTION: To prevent UPS overload and loss of data, make sure your UPS satisfies the requirements for power listed under Component weights and also under AC line voltage requirements. HP StorageWorks 200 Storage Virtualization System site preparation guide 35 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 36
36 Site requirements - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 37
any necessary electrical work related to site prep. AC line voltage requirements The SVS200 operates on 200 VAC nominal, 20 amps, 50 or 60 Hz, single-phase power. Two power cords connected and is specified in RMS amperes. HP StorageWorks 200 Storage Virtualization System site preparation guide 37 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 38
inputs The system has two separate connections to 200 VAC, single-phase, 20-amp power for one HP SVS200 Controller or four connections for two HP SVS200 Controllers. Each AC input must have its own circuit breaker and must be capable of supporting the entire current demand for a Controller. The AC - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 39
C19/C20 Plug (jumper for UPS) • HP Power cord w/IEC 320-C20 connector and 2.5 m jumper for UPS You can supply your own power cables as long as they meet a 20 amp rating, fit the IEC320-C20 PDU inlets, and meet local codes. HP StorageWorks 200 Storage Virtualization System site preparation guide 39 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 40
HP SVS200 rack requires 20-amp, single-phase 200 VAC power supplied by four power cords with plugs, four receptacles, and four main disconnect devices (circuit breakers). The HP SVS200 comes from the HP Do not apply power until instructed to do so by HP. An HP representative should be present - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 41
is also required for the neutral conductor. Your electrician should know the appropriate code requirements for your location/site and wire power distribution to the HP SVS200 accordingly. HP StorageWorks 200 Storage Virtualization System site preparation guide 41 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 42
to ensure power fault tolerance. Single-phase power cable wiring is shown in the figure below. CAUTION: Do not apply power until instructed to do so by HP. An HP representative should be present whenever the system is being connected to a new power source. CAUTION: Be sure to connect the power cords - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 43
from HP, contact your HP sales representative, who will trace your order and expedite delivery. CAUTION: Before delivery, make sure your site meets the requirements explained under the heading, Delivery space requirements. HP StorageWorks 200 Storage Virtualization System site preparation guide 43 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 44
will make sure any damaged components are replaced, regardless of the circumstances and without waiting for any claim settlements. Unpacking the equipment HP representatives will supervise the unpacking and moving of the system equipment. It is your responsibility to receive, unpack, and move the - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 45
without HP supervision, follow the instructions in this HP sales representative immediately if any items are missing or are not the ones you ordered. 4. Move all equipment to the computer room before the installation date. HP StorageWorks 200 Storage Virtualization System site preparation guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 46
easily and contains very sensitive electronic and mechanical components. When you move the rack on its casters, the rolling surface must be able to support the equipment weight and must be free of surface conditions that could cause shock or vibration to the cabinet contents. Avoid pushing the rack - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 47
then remove the crate panels. WARNING! Crate clamps are under tension. Wear safety glasses and hold onto the clamp with your free hand during removal. HP StorageWorks 200 Storage Virtualization System site preparation guide 47 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 48
6mm hex and 19mm wrench, remove the adapter plates that anchor the cabinet to the pallet. 8. Remove the poly bag covering the cabinet (7). 9. Following the instructions provided on the wooden ramp, attach the ramp to the pallet and roll the cabinet onto the floor. 10. Visually check the unit for any - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 49
problems on a system and automatically reports them to the HP STC. Continuous Access The HP can occur and the greater throughput to the applications. XP systems support a range of cache memory. In the event of power loss, HP StorageWorks 200 Storage Virtualization System site preparation guide 49 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 50
(CUs). CUs are numbered sequentially. The system supports a certain number of CUs, depending on the system hardware that houses the channel adapters and service processor (SVP). The unit responsible for single large pool of storage. The LUSE feature is available when the HP StorageWorks LUN Confi - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 51
, host mode 08 represents an HP-UX host. Using two or more storage. Logically speaking, an environment where instances can be executed. Physically, a processor, which is an element of a cluster system. Nonvolatile storage. HP StorageWorks 200 Storage Virtualization System site preparation guide - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 52
XP family members. Consult the owner's guide or your HP representative for the details of which RAID levels are supported by your specific XP system. Random access memory. HP StorageWorks RAID Manager XP, a command line interface for managing XP systems. Remote service information message. Read/write - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 53
the system. SVP use is reserved for HP support representatives only. Terabyte. Transmission control protocol/Internet protocol Target ID. Volume size customization. Synonymous with CVS. Volume ID. Synonymous with LDEV. HP StorageWorks 200 Storage Virtualization System site preparation guide 53 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 54
54 Glossary - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 55
servicing hazards, 21 ESD, 20, 29 F fire safety, 21 floor clearances, 24 conductive, 20 covering, 23 cutouts, 22, 24 earth grounding, 20 grid panels, 22 grounding, 20, 22 tiles, and metallic particulate contamination, 31 waxed, 20 floor plan, 22 HP StorageWorks 200 Storage Virtualization System - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 56
, conductive, 20 G grid panels, floor, 22 grounding, 33, 34, 42 H hazards, servicing, 21 help obtaining, 7, 10 help, obtaining, 10 HP, 45 Subscriber's choice web site, 7 technical support, 7 HP representatives airborne contaminants, 31 and electrical requirements, 33 building construction, 22 - HP 200 | HP StorageWorks 200 Storage Virtualization System site preparation guid - Page 57
unpacking, 44 vibration specifications, 30 T technical support HP, 7 service locator web site, 8 temperature, 28 text HP, 8 HP Subscriber's choice, 7 weights, 17, 18 wet bulb temperature, 29 windows, in the computer room, 20 HP StorageWorks 200 Storage Virtualization System site preparation guide
HP StorageWorks 200 Storage Virtualization
System site preparation guide
This guide describes how to prepare your site for the HP StorageWorks 200 Storage Virtualization System.
Part number: AE071-96003
Second edition: October 2006