LG HMC030KD1 Service Manual - Page 10

length, elevation

Page 10 highlights

Pipe length and the elevation Capacity (Btu/h) 30k (50Hz, 60Hz) Pipe Size GAS LIQUID 5/8" 3/8" Standard Length m(ft) 7.5(25) Max. Elevation © m(ft) 15(50) Max. Length 0 m(ft) 30(100) Additional Refrigerant g/m(oz/ft) 30(0.32) Outdoor unit Indoor unit Outdoor unit Oil trap Indoor unit .1 In case more than 5m (16.4ft) * Capicity is based on standard length and maximum allowance length is the basis of reliability. * Oil trap should be installed per 5-7 meters(16.4-23.0ft). -10-

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

Pipe
length
and
the
elevation
Capacity
(Btu/h)
Pipe
Size
Standard
Length
m(ft)
Max.
Elevation
©
m(ft)
Max.
Length
0
m(ft)
Additional
Refrigerant
g/m(oz/ft)
GAS
LIQUID
30k
(50Hz,
60Hz)
5/8"
3/8"
7.5(25)
15(50)
30(100)
30(0.32)
Indoor
unit
Outdoor
unit
Oil
trap
Indoor
unit
1
.
Outdoor
unit
In
case
more
than
5m
(16.4ft)
*
Capicity
is
based
on
standard
length
and
maximum
allowance
length
is
the
basis
of
reliability.
*
Oil
trap
should
be
installed
per
5-7
meters(16.4-23.0ft).
-10-