LG HMC030KD1 Service Manual - Page 23

Flaring, Connection, Piping

Page 23 highlights

2. Flaring Work and Connection of Piping 1) Flaring work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. 1. Cut the pipes and the cable. • Use the piping kit accessory or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than measured distance. • Cut the cable 1.5m(59.1") longer than the pipe length. Copper pipe 0 X 90/-1, Slanted Uneven Rough Ej 2. Burrs removal • Completely remove all burrs from the cut cross section of pipe/tube. • Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing. Pipe Reamer Point down 4. Flaring work • Carry out flaring work using flaring tool as shown below. Outside diameter mm inch 06.35 1/4 09.52 3/8 012.7 1/2 015.88 5/8 A mm 0 - 0.5 0 - 0.5 0 - 0.5 0 - 1.0 Firmly hold copper pipe in a die in the dimension shown in the table above. Handle Bar Bar O Yoke Cone Copper pipe Clamp handle Red arrow mark 5. Check • Compare the flared work with figure below. • If flare is noted to be defective, cut off the flared section and do flaring work again. 3. Putting nut on • Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work) Flare nut 11 Copper tube Smooth all round Inside is shiny without scratches Even ength all round Improper flaring 1-1 Inclined Surface Cracked Uneven damaged thickness - 23 -

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

2.
Flaring
Work
and
Connection
of
Piping
1)
Flaring
work
Main
cause
for
gas
leakage
is
due
to
defect
in
flar-
ing
work.
Carry
out
correct
flaring
work
in
the
follow-
ing
procedure.
1.
Cut
the
pipes
and
the
cable.
Use
the
piping
kit
accessory
or
the
pipes
purchased
locally.
Measure
the
distance
between
the
indoor
and
the
outdoor
unit.
Cut
the
pipes
a
little
longer
than
measured
distance.
Cut
the
cable
1.5m(59.1")
longer
than
the
pipe
length.
Copper
pipe
0
X
90/-1,
Slanted
Uneven
Rough
Ej
2.
Burrs
removal
Completely
remove
all
burrs
from
the
cut
cross
section
of
pipe/tube.
Put
the
end
of
the
copper
tube/pipe
in
a
down-
ward
direction
as
you
remove
burrs
in
order
to
avoid
dropping
burrs
into
the
tubing.
Pipe
Reamer
Point
down
3.
Putting
nut
on
Remove
flare
nuts
attached
to
indoor
and
outdoor
unit,
then
put
them
on
pipe/tube
having
complet-
ed
burr
removal.
(not
possible
to
put
them
on
after
flaring
work)
Flare
nut
11
Copper
tube
4.
Flaring
work
Carry
out
flaring
work
using
flaring
tool
as
shown
below.
Outside
diameter
A
mm
inch
mm
06.35
1/4
0
-
0.5
09.52
3/8
0
-
0.5
012.7
1/2
0
-
0.5
015.88
5/8
0
-
1.0
Firmly
hold
copper
pipe
in
a
die
in
the
dimension
shown
in
the
table
above.
Bar
Bar
Copper
pipe
Clamp
handle
O
Handle
Yoke
Cone
Red
arrow
mark
5.
Check
Compare
the
flared
work
with
figure
below.
If
flare
is
noted
to
be
defective,
cut
off
the
flared
section
and
do
flaring
work
again.
-
23
-
Smooth
all
round
Even
ength
al
l
round
Inside
is
shiny
without
scratches
Improper
flaring
1-1
Inclined
Surface
Cracked
Uneven
damaged
thickness