LG HMC030KD1 Service Manual - Page 34

Purging

Page 34 highlights

4. AIR PURGING 1) Air purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. ■ Pressure in the system rises. ■ Operating current rises. ■ Cooling(or heating) efficiency drops. ■ Moisture in the refrigerant circuit may freeze and block capillary tubing. ■ Water may lead to corrosion of parts in the refrig- eration system. Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system. • Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. ■ After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder. Indoor unit 2) Air purging with vacuum pump 1. Preparation ■ Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage. 30K Outdoor unit 2. Leak test ■ Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses. A CAUTION Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close. ■ Pressurize the system to no more than 150 P.S.I.G with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap. A\ CAUTION To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. Manifold valve Pressure gauge Charge hos Nitrogen gas cylinder(in vertical standing position) - 34 -

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

4.
AIR
PURGING
1)
Air
purging
Air
and
moisture
remaining
in
the
refrigerant
system
have
undesirable
effects
as
indicated
below.
Pressure
in
the
system
rises.
Operating
current
rises.
Cooling(or
heating)
efficiency
drops.
Moisture
in
the
refrigerant
circuit
may
freeze
and
block
capillary
tubing.
Water
may
lead
to
corrosion
of
parts
in
the
refrig-
eration
system.
Therefore,
the
indoor
unit
and
tubing
between
the
indoor
and
outdoor
unit
must
be
leak
tested
and
evacuated
to
remove
any
noncondensables
and
moisture
from
the
system.
2)
Air
purging
with
vacuum
pump
1.
Preparation
Check
that
each
tube(both
liquid
and
gas
side
tubes)
between
the
indoor
and
outdoor
units
have
been
properly
connected
and
all
wiring
for
the
test
run
has
been
completed.
Remove
the
service
valve
caps
from
both
the
gas
and
the
liquid
side
on
the
outdoor
unit.
Note
that
both
the
liquid
and
the
gas
side
service
valves
on
the
outdoor
unit
are
kept
closed
at
this
stage.
2.
Leak
test
Connect
the
manifold
valve(with
pressure
gauges)
and
dry
nitrogen
gas
cylinder
to
this
service
port
with
charge
hoses.
A
CAUTION
Be
sure
to
use
a
manifold
valve
for
air
purging.
If
it
is
not
available,
use
a
stop
valve
for
this
purpose.
The
"Hi"
knob
of
the
manifold
valve
must
always
be
kept
close.
Pressurize
the
system
to
no
more
than
150
P.S.I.G
with
dry
nitrogen
gas
and
close
the
cylinder
valve
when
the
gauge
reading
reached
150
P.S.I.G.
Next,
test
for
leaks
with
liquid
soap.
A\
CAUTION
To
avoid
nitrogen
entering
the
refrigerant
system
in
a
liquid
state,
the
top
of
the
cylinder
must
be
higher
than
its
bottom
when
you
pressurize
the
system.
Usually,
the
cylinder
is
used
in
a
vertical
standing
position.
-
34
-
Do
a
leak
test
of
all
joints
of
the
tubing(both
indoor
and
outdoor)
and
both
gas
and
liquid
side
service
valves.
Bubbles
indicate
a
leak.
Be
sure
to
wipe
off
the
soap
with
a
clean
cloth.
After
the
system
is
found
to
be
free
of
leaks,
relieve
the
nitrogen
pressure
by
loosening
the
charge
hose
connector
at
the
nitrogen
cylinder.
When
the
system
pressure
is
reduced
to
normal,
disconnect
the
hose
from
the
cylinder.
Indoor
unit
30K
Outdoor
unit
Manifold
valve
Pressure
gauge
Charge
hos
Nitrogen
gas
cylinder(in
vertical
standing
position)