LG HMC036KDT1 Service Manual - Page 34
Cycle, Troubleshooting, Guide, Trouble, analysis, Multi, Conditioner
View all LG HMC036KDT1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 34 highlights
Cycle Troubleshooting Guide I Cycle Troubleshooting Guide Trouble analysis 1. Check temperature difference between intake and discharge air and operating current. Temp. Difference Operating Current Temp. difference : approx. 0°C Current : less than 80% of rated current All amount of refrigerant leaked out. Check refrigeration cycle. Temp. difference : approx. 8°C Current : less than 80% of rated current Refrigerant leakage Clog of refrigeration cycle Defective compressor Temp. difference : less than 8°C Current :over the rated current Excessive amount of refrigerant Temp. difference : over 8°C Normal Notice: Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Higher Temperature (Compared with the normal value) High Normal Lower Higher Cause of Trouble Description Defective compressor Current is low. Defective 4-way reverse valve Excessive amount of refrigerant High pressure does not quickly rise at the beginning of operation. Insufficient amount of refrigerant(Leakage) Clogging Current is low. Current is low. Notice: 1. The suction pressure is usually 4.5-6.0 kg/cm'G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty. 34 MPS Multi Air Conditioner