ENGLISH Installation of Indoor, Outdoor Unit Piping length and elevation Multi Piping Type Outdoor Unit Capacity (Btu/h class) 18k Max total length of all pipes (A+B)/(A+B+C)/ (A+B+C+D) 50(164) Max length of each pipe (A/B/C/D) 25(82) 24k 75(246) 25(82) 36k 75(246) 25(82) Min length of each pipe (A/B/C/D) 3(10) 3(10) 3(10) Unit : m(ft) Max Elevation between each indoor unit and outdoor unit (h1) Max elevation between indoor units (h2) Max.Combination of Indoor unit (Btu/h class) 15(49) 7.5(25) 24k 15(49) 7.5(25) 33k 15(49) 7.5(25) 48k Indoor unit Capacity (Btu/h class) 9k 12k 18k Pipe Diameter Unit : mm(inch) Gas Liquid 9.52(3/8) 6.35(1/4) 9.52(3/8) 6.35(1/4) 12.7(1/2) 6.35(1/4) Standard Pipe Length Unit : m(ft) 7.5(25) 7.5(25) 7.5(25) Additional Refrigerant Unit : g/m(oz/ft) 20(0.22) 20(0.22) 20(0.22) A B h2 C h1 D CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Installation Manual 11