Maytag MER5775RAB Installation Manual - Page 7

Emo, E, Conddit.

Page 7 highlights

CONNECTING THE RANGE FIGURE 7 4-Wire Service Cord or Conduit Installation (Mobile Homes Or As Required By Codes) 1. The copper ground strap connected between the neutral (middle) post of the main terminal block and the chassis MUST be cut off as shown in figure 7. Save the green ground screw to attach the ground from the 4 wire cord. Only a 4 wire cord or conduit should be used. 2. If bare copper or aluminum wiring is used, attach adapter lugs as shown in figure 7. (See Bare Wire Connection). Torque specifications are shown below. 3. The ground wire from the service cord or conduit must connect to the range chassis using the green ground screw. 4. The white wire of the service cord or conduit must connect to the neutral (middle) post of the main terminal block. The other two wires of the service cord connect to the red and black posts of the main terminal block, respectively. If using bare wire, attach wire to appropriate lug as shown. Torque specifications are shown below. 5. An appropriate strain relief for service cord or conduit MUST be attached to the conduit plate. Conversion From 3-Wire To 4-Wire Service (Free-standing Model With 3-Wire Service Cord Attached), Disconnect range from power. Remove the access cover on back of range and remove the 3-wire service cord from the main terminal block. Follow instructions as outlined in figure 7 to connect the 4-wire service cord. NOTE: Cord replacement - ONLY a power supply cord rated at 240 volts minimum, 40 amperes or 50 amperes power supply cord that is marked for use with nominal 1 3/8" (34.93 mm) diameter connection opening, with closed loop terminals and marked for use with ranges shall be used. ACCEPTABLE - 4 WIRE PLUG INSTALLATION RED WHITE BLACK TERMINAL CONNECTION BLOCK CONDUIT PLATE /' /" / CHASSIS GROUND THIS PORTION GROUNDING STRAP MUST 8E REMOVED, STRAIN RELIEF 1-1t2 (3.8 CM) MINIMUM } MIDDLE WIRE OF SERVICE CORD OR CONDUIT FLOOR _U BARE WIRE CONNECTION RED WHITE ADAPTER / LUGS LOCATED IN LITERATURE HIT BLACK BARF WIRE IOROHF SPF_IFICATIONS tgG ATTACHEOTO TERMINAL BLOCK " 20 IN-LB _LL.ILLA_ ZOLOJ_ 8 35 IN-LB 10A-L14[ERRATIVF INSTAZOIIINA'LTBION ,EMoW,IFCEUONDDIT. > BRACKET, FLIP & RE-ATTACH WITH SMALL HOLE VISIBLE. RECEPTACLE MOUNTED FLUSH TO WALL OUTLET RECEPTACLE TO BE ROTATED AS SHOWN IF NOT FLUSH TO WALL FIGURE 7 -7-

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21

CONNECTING
THE
RANGE
FIGURE
7
4-Wire
Service
Cord
or Conduit
Installation
(Mobile
Homes Or As Required
By Codes)
1. The copper ground strap connected
between the
neutral (middle)
post of the main terminal block and the
chassis
MUST be cut off as shown in figure 7. Save the
green ground screw
to attach the ground from the 4
wire cord. Only a 4 wire cord or conduit should be
used.
2. If bare copper or aluminum
wiring is used, attach
adapter lugs as shown in figure 7. (See Bare Wire
Connection).
Torque specifications
are shown below.
3. The ground wire from the service
cord or conduit must
connect to the range chassis using the green ground
screw.
4. The white wire of the service
cord or conduit must
connect to the neutral (middle)
post of the main
terminal
block. The other two wires of the service
cord
connect to the red and black posts of the main terminal
block, respectively.
If using bare wire, attach wire to
appropriate
lug as shown. Torque specifications
are
shown below.
5. An appropriate
strain relief for service
cord or conduit
MUST be attached to the conduit
plate.
Conversion
From
3-Wire
To 4-Wire
Service
(Free-standing
Model With 3-Wire
Service Cord
Attached),
Disconnect
range from power. Remove
the access
cover
on back of range and remove the 3-wire service
cord from
the main terminal
block. Follow instructions
as outlined in
figure 7 to connect the 4-wire service
cord.
NOTE:
Cord replacement
-
ONLY
a power supply cord
rated at 240 volts minimum,
40 amperes
or 50 amperes
power supply cord that is marked for use with nominal 1
3/8" (34.93 mm) diameter
connection
opening, with
closed loop terminals
and marked for use with ranges
shall be used.
ACCEPTABLE
- 4 WIRE
PLUG
INSTALLATION
RED
WHITE
BLACK
CHASSIS
GROUND
STRAIN
RELIEF
RECEPTACLE
MOUNTED
FLUSH
TO
WALL
1-1t2
(3.8
CM)
MINIMUM
}
TERMINAL
/'
CONNECTIONBLOCK
/"
/
CONDUIT
PLATE
THIS
PORTION
GROUNDING STRAP
MUST
8E REMOVED,
FLOOR
MIDDLE WIRE
OF
SERVICE
CORD
OR
CONDUIT
/
BARE
WIRE
CONNECTION
WHITE
ADAPTER
LUGS
LOCATED
IN
LITERATURE
HIT
BLACK
BARF
WIRE
IOROHF
SPF_IFICATIONS
tgG
ATTACHEO
TO TERMINAL BLOCK
"
20
IN-LB
_LL.ILLA_
ZOLOJ_
_U
10-14
ZO
IN'LB
8
35
IN-LB
AL[ERRATIVF INSTAIIATION
,EMo, E
WIFU
CONDDIT.
>
BRACKET, FLIP
&
RE-ATTACH WITH SMALL
HOLEVISIBLE.
OUTLET RECEPTACLE TO BE
ROTATED AS SHOWN
IF
NOT
FLUSH TO
WALL
RED
FIGURE
7
-7-