Campbell Scientific CR1000KD CR800 and CR850 Measurement and Control Systems - Page 519
Setting, Description, Default Entry
View all Campbell Scientific CR1000KD manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 519 highlights
Appendix B. Status Table and Settings Table 118. CR800 Settings Settings are accessed through the Campbell Scientific Device Configuration Utility (DevConfig) via direct-serial and IP connections, or through PakBusGraph via most CR800 supported telecommunications options. Setting Description Default Entry Route Filters Baud Rate Applies to the following communication ports: RS232 ME SDC7 SDC8 SDC10 SDC11 COM1 COM2 This setting configures the CR800 to restrict routing or processing of some PakBus® message types so that a "state changing" message can only be processed or forwarded by this CR800 if the source address of that message is in one of the source ranges and the destination address of that message is in the corresponding destination range. If no ranges are specified (the default), the CR800 will not apply any routing restrictions. "State changing" message types include set variable, table reset, file control send file, set settings, and revert settings. For example, if this setting was set to a value of (4094, 4094, 1, 10), the CR800 would only process or forward "state changing" messages that originated from address 4094 and were destined to an address in the range between one and ten. This is displayed and parsed using the following formal syntax: route-filters := { "(" source-begin "," source-end "," dest-begin "," dest-end ")" }. source-begin := uint2. ; 1 < source-begin