Dell S5296F-ON EMC PowerSwitch S5200F-ON Series Setup Guide - Page 20

DC Power Connector and Wiring Block, DC Power Connector Ground

Page 20 highlights

Figure 19. DC Power Connector and Wiring Block 1. DC wire RTN 3. Captive screws (2) 5. PSU status LED 7. DC wire -48V 2. DC power connector 4. Orange tab 6. DC power socket Figure 20. DC Power Connector Ground 1. Ground nut 3. Lock washer 5. Device grounding rod 2. Washer 4. Ground cable To connect a DC PSU to the site's DC power source, follow these steps: 1. Strip 1/2 inches of insulation from each of the power connector's wires, as shown. 2. Insert each of the power connector's bare wire lengths into the wiring block, as shown. 3. Use a flat-blade screwdriver to tighten the screws that secures the bare wires into the wiring block. 4. Secure the site's DC power source wires to the other side of the wiring block (See steps 1 and 3). 5. Insert the DC power connector into the power socket of the DC PSU. Ensure that the connector pins firmly seat and you hear the click of the power connector's left and right levered clamps lock into place. 20 S5200F-ON Series switch Installation

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

Figure 19. DC Power Connector and Wiring Block
1.
DC wire RTN
2.
DC power connector
3.
Captive screws (2)
4.
Orange tab
5.
PSU status LED
6.
DC power socket
7.
DC wire –48V
Figure 20. DC Power Connector Ground
1.
Ground nut
2.
Washer
3.
Lock washer
4.
Ground cable
5.
Device grounding rod
To connect a DC PSU to the site’s DC power source, follow these steps:
1.
Strip 1/2 inches of insulation from each of the power connector’s wires, as shown.
2.
Insert each of the power connector’s bare wire lengths into the wiring block, as shown.
3.
Use a flat-blade screwdriver to tighten the screws that secures the bare wires into the wiring block.
4.
Secure the site’s DC power source wires to the other side of the wiring block (See steps 1 and 3).
5.
Insert the DC power connector into the power socket of the DC PSU. Ensure that the connector pins firmly seat and you hear the
click of the power connector’s left and right levered clamps lock into place.
20
S5200F-ON Series switch Installation