Fluke 345 FE 345 Users Manual - Page 21

VAR Measurement Single and 3 Phase, Power Factor Single and 3 Phase, Kilowatt Hour kWHr - power meter

Page 21 highlights

Power Quality Clamp Meter Specifications VAR Measurement (Single and 3 Phase) Measuring range 0 - 1200 kVAR Autorange facility 4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR Resolution 1 VAR in 4 kVAR range 10 VAR in 40 kVAR range 100 VAR in 400 kVAR range 1 kVAR in 1200 kVAR range Accuracy VAR > 4 kVAR 2.5 % rdg ± 5 digits VAR < 4 kVAR 0.25 kVAR Power Factor range 0.3 < PF < 0.99 Power Factor (Single and 3 Phase) Power Factor Measuring range 0.3 cap ... 1.0 ... 0.3 ind (72.5° capacitive ... 0° ... 72.5° inductive) Resolution 0.001 Accuracy 3 ° Frequency range 15 Hz to 1 kHz Displacement Power Factor Measuring range 0.3 cap ... 1.0 ... 0.3 ind (72.5 ° capacitive ... 0° ... 72.5 ° inductive) Resolution 0.001 Accuracy 3 ° Frequency ranges 15 Hz to 22 Hz and 45 Hz to 65 Hz Kilowatt Hour (kWHr) Measuring range 40,000 kWHr Autorange facility 4 kWHr, 40 kWHr, 400 kWHr, 4,000 kWHr, 40,000 kWHr Resolution 1 WHr in 4 kWHr range 10 WHr in 40 kWHr range 100 WHr in 400 kWHr range 1 kWHr in 4,000 kWHr range 10 kWHr in 40,000 kWHr range 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80

Power Quality Clamp Meter
Specifications
7
VAR Measurement (Single and 3 Phase)
Measuring range
.................................................
0 – 1200 kVAR
Autorange facility
................................................
4 kVAR, 40 kVAR, 400 kVAR, 1200
kVAR
Resolution
...........................................................
1 VAR in 4 kVAR range
10 VAR in 40 kVAR range
100 VAR in 400 kVAR range
1 kVAR in 1200 kVAR range
Accuracy
VAR > 4 kVAR
................................................
± 2.5 % rdg ± 5 digits
VAR < 4 kVAR
................................................
± 0.25 kVAR
Power Factor range
............................................
0.3 < PF < 0.99
Power Factor (Single and 3 Phase)
Power Factor
Measuring range
............................................
0.3 cap … 1.0 … 0.3 ind
(72.5° capacitive ... 0° ... 72.5°
inductive)
Resolution
.......................................................
0.001
Accuracy
.........................................................
± 3 °
Frequency range 15 Hz to 1 kHz
Displacement Power Factor
Measuring range
............................................
0.3 cap … 1.0 … 0.3 ind
(72.5 ° capacitive ... 0° ... 72.5 °
inductive)
Resolution
.......................................................
0.001
Accuracy
.........................................................
± 3 °
Frequency ranges
..........................................
15 Hz to 22 Hz and 45 Hz to 65 Hz
Kilowatt Hour (kWHr)
Measuring range
.................................................
40,000 kWHr
Autorange facility
................................................
4 kWHr, 40 kWHr, 400 kWHr, 4,000
kWHr, 40,000 kWHr
Resolution
...........................................................
1 WHr in 4 kWHr range
10 WHr in 40 kWHr range
100 WHr in 400 kWHr range
1 kWHr in 4,000 kWHr range