Parameter, VAC 50, Hz only, or 60 Hz, Table 20 DKU power specifications, 50-amp, single-phase
![]() |
View all HP XP20000/XP24000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 47 highlights
Parameter 200 VAC 50 or 60 Hz 208 VAC 60 Hz only 220 VAC 50 Hz only 230 VAC 50 or 60 Hz 240 VAC 50 Hz only 380 VAC 50 Hz only 400 VAC 50 Hz only 415 VAC 50 Hz only Number of power cords 2 2 2 2 2 2 2 2 Recommended circuit breakers (amps) 30 30 30 30 30 30 30 30 Number of circuit breakers 2 2 2 2 2 2 2 2 Table 20 DKU power specifications, 50-amp, 50 or 60 Hz, single-phase Parameter 200 VAC 50 or 60 Hz 208 VAC 60 Hz only 220 VAC 50 Hz only 230 VAC 50 or 60 Hz 240 VAC 50 Hz only Minimum operating voltage (VAC) Maximum operating voltage (VAC) Rated line current per power cord (Amps rms) Number of power cords Recommended circuit breakers (amps) Number of circuit breakers 184 212 17.8 2 50 2 191 220 17.2 2 50 2 202 233 16.2 2 50 2 212 221 244 15.5 2 50 2 254 14.8 2 50 2 Table 21 DKU power specifications, 30-amp, 50 or 60 Hz, single-phase Parameter 200 VAC 50 208 VAC 60 or 60 Hz Hz only 220 VAC 50 Hz only 230 VAC 50 or 60 Hz 240 VAC 50 Hz only Minimum operating voltage (VAC) 184 191 202 212 221 XP24000/XP20000 Disk Array Site Preparation Guide 47