Honeywell NS2 Configuration Guide - Page 13

RS-485 Short Haul Modem Connection

Page 13 highlights

Honeywell Access Systems RS-485 Short Haul Modem Connection Thirty-one NS2 panels for each drop line. NStar Server RS-232, 50 Ft. Max. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN) NS2 Configuration Guide SHM-B-ASYNC Short Haul Modem RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (Null) 2 (TX) 2 (RX) 3 (RX) or 3 (TX) 7 (GND) 7 (GND) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) 5279.9 Feet NS2 Panel NS2 Panel See RS-485 Cable note. EG EG Only Earth Ground (EG) EG one side of cable. EG It is recommended to earth ground (EG) each NS2 Enclosure individually. SHM-B-ASYNC Short Haul Modem DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) N-485-PCI-2 RS-232, 50 Ft. Max. Male 9 Pin Male 25 Pin Refer to 485-PCI/NS2 Panel Connection Detail diagram. RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (Null) 2 (TX) 2 (RX) 3 (RX) or 3 (TX) 7 (GND) 7 (GND) 7-101004-01 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

7-101004-01
13
Honeywell Access Systems
NS2 Configuration Guide
RS-485 Short Haul Modem Connection
Thirty-one NS2 panels for each drop line.
EG
NS2
Panel
NS2
Panel
NStar Server
RS-232, 50 Ft. Max.
RS-232, 50 Ft. Max.
N-485-PCI-2
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
It is recommended to earth ground (EG)
each NS2 Enclosure individually.
Only Earth Ground (EG)
one side of cable.
EG
EG
EG
Refer to 485-PCI/NS2
Panel Connection
Detail diagram.
RS232 Cable
2 TX
3 RX
DTE
(Straight)
2 (TX)
3 (RX)
7 (GND)
DCE
(Null)
2 (RX)
3 (TX)
7 (GND)
PC
(DB-9)
MODEM
5 Comm
or
RS232 Cable
2 TX
3 RX
DTE
(Straight)
2 (TX)
3 (RX)
7 (GND)
DCE
(Null)
2 (RX)
3 (TX)
7 (GND)
PC
(DB-9)
MODEM
5 Comm
or
Male 9 Pin
Male 25 Pin
5279.9 Feet
SHM-B-ASYNC
Short Haul Modem
SHM-B-ASYNC
Short Haul Modem
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
RS-485
Red/White
Black/Green
RS-485 COM
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
RS-485 Cable
See RS-485
Cable note.