Honeywell NS2 Configuration Guide - Page 16

M-56K Dial-up Modem, RS-485 Connection

Page 16 highlights

NS2 Configuration Guide M-56K Dial-up Modem, RS-485 Connection Thirty-one NS2 panels for each drop line. Honeywell Access Systems NStar Server Refer to 485-PCI/ NS2 Panel Connection Detail diagram. N-485-HUB-2 COM Port Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Straight Thru Cable M-56K FAX/MODEM Local DIP Switch Settings (1, 3, 5, 8 ON) (2, 4, 6, 7 OFF) Male 25 Pin 3 (RX) 2 (TX) 7 (Comm) RS-232 (50 Ft.) RS-485 (4,000 Ft.) M-56K FAX/MODEM Remote DIP Switch Settings (1, 3, 8 ON) (2, 4, 5, 6, 7 OFF) Analog Phone Line Dedicated analog phone line recommended DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) EG DB 9 / DB 25 Connectors Female Male NS2 Panel NS2 Panel EG See RS-485 Cable note. Only Earth Ground (EG) EG one side of cable. EG It is recommended to earth ground (EG) each NS2 Enclosure individually. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN) 16 7-101004-01

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

NS2 Configuration Guide
Honeywell Access Systems
16
7-101004-01
M-56K Dial-up Modem, RS-485 Connection
Thirty-one NS2 panels for each drop line.
NStar Server
M-56K
M-56K
FAX/MODEM
FAX/MODEM
Local DIP Switch Settings
(1, 3, 5, 8 ON) (2, 4, 6, 7 OFF)
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
N-485-HUB-2
NS2
Panel
NS2
Panel
Refer to
485-PCI/
NS2 Panel
Connection
Detail
diagram.
Dedicated analog phone
line recommended
Analog Phone Line
RS-485 (4,000 Ft.)
RS-232 (50 Ft.)
It is recommended to earth ground (EG)
each NS2 Enclosure individually.
Only Earth Ground (EG)
one side of cable.
EG
EG
EG
EG
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
Female 9 Pin
Male 25 Pin
(TX)
3
2
(TX)
(Comm)
5
7
(Comm)
(RX)
2
3
(RX)
Straight Thru Cable
COM Port
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
RS-485
Red/White
Black/Green
RS-485 COM
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
RS-485 Cable
See RS-485
Cable note.
Female
Male
DB 9 / DB 25
Connectors