Honeywell NS2 Configuration Guide - Page 17

Fiber Converter to RS-485 Connection

Page 17 highlights

Honeywell Access Systems Fiber Converter to RS-485 Connection Thirty-one NS2 panels for each drop line. NS2 Configuration Guide COM Port Refer to 485-PCI/NS2 Panel Connection Detail diagram. RS-232 (50 Ft. Max.) RS-485 (4000 Ft. Max.) NStar Server N-485-PCI-2 FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD Fiber Wire 10,000 Ft. FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD NS2 EG Panel NS2 Panel TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -) RS-485 Drain Wire Floating EG DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak) S7: ON S8: OFF (19,200 Baud Rate) N-485-PCI-2 (485 Common) (RED/WHITE) (BLACK/GREEN) RS-485 Drain Wire to earth ground RS-485 Drain not connected here (connected at panel side) NS2 Panel TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -) Fiber Wire 10,000 Ft. RS-485 Drain not connected here (floating) NS2 Panel TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -) NS2 Panel NS2 EG Panel See RS-485 Cable note. FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD EG It is recommended to earth ground (EG) each NS2 enclosure individually. EG DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) EG FC485 RS-485 Positive (+) RS-485 Negative (-) RS-485 Common RS-485 Drain not connected RS-485 Cable NS2 Panel TB9-1 (RS485+) TB9-2 (RS485-) TB9-3 (RS485 COM) RS-485 Drain wire grounded NS2 Panel TB9-1 (RS485+) TB9-2 (RS485-) TB9-3 (RS485 COM) RS-485 Drain wire grounded 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN) 7-101004-01 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

7-101004-01
17
Honeywell Access Systems
NS2 Configuration Guide
Fiber Converter to RS-485 Connection
Thirty-one NS2 panels for each drop line.
NStar Server
N-485-PCI-2
NS2
Panel
Fiber Wire
10,000 Ft.
COM Port
RS-232 (50 Ft. Max.)
EG
EG
EG
EG
EG
EG
Refer to 485-PCI/NS2 Panel
Connection Detail diagram.
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak)
S7: ON
S8: OFF (19,200 Baud Rate)
DIP Switch Settings
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
RS-485
(4000 Ft. Max.)
It is recommended to
earth ground (EG)
each NS2 enclosure
individually.
RS-485 Comm.
RXD
PWR
TXD
RS-485 Positive(+)
RS-485 Negitive (-)
Fiber TXD
Fiber RXD
FC485
RS-485 Fiber Converter
TB9-1 (RS485 +)
TB9-2 (RS485 -)
NS2 Panel
RS-485 Drain Wire Floating
TB9-3 (RS485 Comm)
Fiber Wire
10,000 Ft.
TB9-1 (RS485 +)
TB9-2 (RS485 -)
TB9-3 (RS485 Comm)
NS2 Panel
RS-485 Drain
not connected here
(connected at panel side)
RS-485 Comm.
RXD
PWR
TXD
RS-485 Positive(+)
RS-485 Negitive (-)
Fiber TXD
Fiber RXD
FC485
RS-485 Fiber Converter
NS2
Panel
NS2
Panel
RS-485 Comm.
RXD
PWR
TXD
RS-485 Positive(+)
RS-485 Negitive (-)
Fiber TXD
Fiber RXD
FC485
RS-485 Fiber Converter
TB9-1 (RS485 +)
TB9-2 (RS485 -)
TB9-3 (RS485 Comm)
NS2 Panel
RS-485 Drain
not connected here
(floating)
RS-485 Comm.
RXD
PWR
TXD
RS-485 Positive(+)
RS-485 Negitive (-)
Fiber TXD
Fiber RXD
FC485
RS-485 Fiber Converter
(485 Common)
(RED/WHITE)
(BLACK/GREEN)
N-485-PCI-2
RS-485 Drain Wire to earth ground
See RS-485
Cable note.
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
RS-485 Drain wire
grounded
FC485
RS-485 Positive (+)
RS-485 Negative (-)
RS-485 Common
RS-485 Drain not
connected
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
RS-485 Drain wire
grounded
RS-485 Cable