Honeywell NS2 Configuration Guide - Page 8

RS-485 Connection - parts

Page 8 highlights

NS2 Configuration Guide RS-485 Connection Thirty-one NS2 panels for each drop line. Honeywell Access Systems NStar Server COM Port RS-232 (50 Ft. Max.) RS-485 (4,000 Ft.) N-485-PCI-2 Refer to 485-PCI / NS2 Panel Connection Detail diagram. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN) DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) NS2 Panel NS2 Panel See RS-485 Cable note. EG EG Only Earth Ground EG one side of cable. EG It is recommended to earth ground (EG) each NS2 enclosure individually. 8 7-101004-01

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

NS2 Configuration Guide
Honeywell Access Systems
8
7-101004-01
RS-485 Connection
Thirty-one NS2 panels for each drop line.
NStar Server
COM Port
RS-232 (50 Ft. Max.)
N-485-PCI-2
RS-485 (4,000 Ft.)
Refer to 485-PCI / NS2 Panel
Connection
Detail diagram.
NS2
Panel
NS2
Panel
Only Earth
Ground
one side of cable.
It is recommended to earth ground (EG)
each NS2 enclosure individually.
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
EG
EG
EG
EG
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
RS-485
Red/White
Black/Green
RS-485 COM
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
RS-485 Cable
See RS-485
Cable note.