Honeywell NS2 Configuration Guide - Page 7

Configuration Diagrams - nstar

Page 7 highlights

Honeywell Access Systems Configuration Diagrams RS-232 Connection One NS2 panel for each COM port. NS2 Configuration Guide NStar Server COM 1 COM 2 CBL50 (RS-232) 50 ft. Max. CBL50 (RS-232) 50 ft. Max. NS2 Panel DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF NS2 Panel 7-101004-01 EG It is recommended to earth ground (EG) each NS2 enclosure individually. EG RS-232 (DB9) 8 CBL50 (RS-232) Request To Send (RTS) RJ-45 2 5 Signal Ground (GND) 3 2 Receive Data (RXD) 4 3 Transmit Data (TXD) 5 7 Clear To Send (CTS) 7 9-Pin COM 1 or COM 2 to RJ-45 on NS2 Panel 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

7-101004-01
7
Honeywell Access Systems
NS2 Configuration Guide
Configuration Diagrams
RS-232 Connection
One NS2 panel for each COM port.
DIP Switch Settings
S1-S5: Panel Address
S6: OFF (RS-485 Disable)
S7: ON (57,600 Baud Rate)
S8-S10: OFF
NStar Server
COM 1
COM 2
NS2
Panel
EG
NS2
Panel
CBL50
(RS-232)
50 ft. Max.
CBL50 (RS-232) 50 ft. Max.
Request To Send (RTS)
CBL50 (RS-232)
Signal Ground (GND)
Receive Data (RXD)
Transmit Data (TXD)
Clear To Send (CTS)
RS-232
(DB9)
RJ-45
8
5
2
3
7
2
3
4
5
7
9-Pin
COM 1 or COM 2 to RJ-45 on NS2 Panel
EG
It is recommended to earth ground (EG)
each NS2 enclosure individually.