Dell Force10 E600i Quick Start Guide - Page 11

Cable Connector Required for E600i DC, Replace the two washers and nuts.

Page 11 highlights

Step Task 3 Attach the grounding cable onto the ground studs. The grounding cable must comply with your local electrical codes in size and color (typically the color is green or green with yellow stripe), NOTE: Grounding cables must be terminated only with a ULlisted 2-hole lug with 1/4-inch holes on 3/4-inch spacing. Cable Connector Required for E600i DC High-strand-count conductor All measurements in inches. 0.750" 0.267 diameter 2 Holes FN00011A 4 Replace the two washers and nuts. 5 With a 7/16-inch box or socket wrench, tighten the nuts to 25 in-lbs. 6 Connect the opposite end of the grounding cable to the nearest appropriate facility grounding post. Installing the Hardware 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50

Installing the Hardware
9
3
Attach the grounding cable onto the ground studs. The grounding cable
must comply with your local electrical codes in size and color (typically
the color is green or green with yellow stripe),
NOTE:
Grounding cables must be terminated only with a UL-
listed 2-hole lug with 1/4-inch holes on 3/4-inch spacing.
Cable Connector Required for E600i DC
4
Replace the two washers and nuts.
5
With a 7/16-inch box or socket wrench, tighten the nuts to 25 in-lbs.
6
Connect the opposite end of the grounding cable to the nearest
appropriate facility grounding post.
Step
Task
0.750"
High-strand-count
conductor
diameter
2 Holes
All measurements in inches.
FN00011A
0.267