HP BL260c HP BladeSystem c-Class Site Planning Guide - Page 52

HP 10000 G2 rack specifications, Rack requirements

Page 52 highlights

Specification Value Height Depth Width 584.00 mm (23.00 in) 1013.00 mm (39.88 in) 607.00 mm (23.88 in) Standard enclosure weight * Unboxed 65.80 kg (145.00 lb) Shipping Maximum enclosure weight Unboxed Shipping 88.50 kg (195.00 lb) 136.00 kg (300.00 lb) 158.80 kg (350.00 lb) * Includes two power supplies, four fans, and one Onboard Administrator. HP 10000 G2 rack specifications For a current list of all rack specifications, see the Best Practices document on the HP website (http://www.hp.com/support/HP10000G2SeriesRack_Manuals). Rack Height Width Depth Dynamic load (gross) Static load HP 10622 22U G2 HP 10636 36U G2 HP 10642 42U G2 HP 10647 47U G2 HP 10842 42U G2 600 mm (23.8 in) 600 mm (23.8 in) 600 mm (23.8 in) 600 mm (23.8 in) 800 mm (31.5 in) 1000 mm (39.4 in) 1000 mm (39.4 in) 1000 mm (39.4 in) 1000 mm (39.4 in) 1000 mm (39.4 in) 544.3 kg (1200 lb) 689.5 kg (1520 lb) 907.2 kg (2000 lb) Not applicable 453.6 kg (1000 lb) 544.3 kg (1200 lb) 907.2 kg (2000 lb) 907.2 kg (2000 lb) 907.2 kg (2000 lb) 907.2 kg (2000 lb) Rack requirements The enclosure is compatible with the following racks: • All HP 10000 and 10000G2 Series racks except the HP 10614 rack. NOTE: The system is optimized for 10000 Series racks. • Telco racks If a third-party rack is used, observe the following additional requirements to ensure adequate airflow and to prevent damage to the equipment: • Front and rear doors: If the rack includes closing front and rear doors, a minimum of 65 percent open area must be provided to ensure adequate airflow. Hardware specifications and requirements 52

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73

Hardware specifications and requirements
52
Specification
Value
Height
584.00 mm (23.00 in)
Depth
1013.00 mm (39.88 in)
Width
607.00 mm (23.88 in)
Standard enclosure weight *
Unboxed
65.80 kg (145.00 lb)
Shipping
88.50 kg (195.00 lb)
Maximum enclosure weight
Unboxed
136.00 kg (300.00 lb)
Shipping
158.80 kg (350.00 lb)
* Includes two power supplies, four fans, and one Onboard Administrator.
HP 10000 G2 rack specifications
For a current list of all rack specifications, see the Best Practices document on the HP website
(
).
Rack
Height
Width
Depth
Dynamic load
(gross)
Static load
HP 10622
G2
22U
600 mm (23.8
in)
1000 mm (39.4
in)
544.3 kg (1200
lb)
544.3 kg (1200
lb)
HP 10636
G2
36U
600 mm (23.8
in)
1000 mm (39.4
in)
689.5 kg (1520
lb)
907.2 kg (2000
lb)
HP 10642
G2
42U
600 mm (23.8
in)
1000 mm (39.4
in)
907.2 kg (2000
lb)
907.2 kg (2000
lb)
HP 10647
G2
47U
600 mm (23.8
in)
1000 mm (39.4
in)
Not applicable
907.2 kg (2000
lb)
HP 10842
G2
42U
800 mm (31.5
in)
1000 mm (39.4
in)
453.6 kg (1000
lb)
907.2 kg (2000
lb)
Rack requirements
The enclosure is compatible with the following racks:
All HP 10000 and 10000G2 Series racks except the HP 10614 rack.
NOTE:
The system is optimized for 10000 Series racks.
Telco racks
If a third-party rack is used, observe the following additional requirements to ensure adequate airflow and
to prevent damage to the equipment:
Front and rear doors: If the rack includes closing front and rear doors, a minimum of 65 percent
open area must be provided to ensure adequate airflow.