HP BL260c HP BladeSystem c-Class Site Planning Guide - Page 55

Example maximum configuration, HP 4X DDR InfiniBand Switch Module for HP c-Class BladeSystem 1

Page 55 highlights

• HP ProLiant BL465c Server Blades (16) o 2.8-GHz AMD Opteron™ Model 2220 processor (2 per server blade) o 8GB (4 x 2GB) RAM per server blade o 72GB 15,000-rpm SAS hard drives (2 per server blade) o QLogic Dual-Port Fibre Channel Mezzanine (1 per server blade) Total system leakage current per branch Total system inrush current per branch (2 mS) Total system weight (includes power and rack) 0 mA 210 A 301 kg (664 lb) Power credentials Total input power Total input VA BTU Total input current Total airflow (CFM) Total airflow (CMM) Idle 2957 W 3017 VA 10083 BTU 14.51 A 262 7.408 100% utilization 4624 W 4718 VA 15767 BTU 22.68 A 349 9.877 Circuit sizing 6244 W 6372 VA 21293 BTU 30.63 A 516 14.611 Example maximum configuration This power summary is based on the following configuration: • HP BladeSystem c7000 Enclosure (1) • HP Virtual Connect Ethernet Modules (2) • HP Virtual Connect Fibre Channel Modules (2) • HP 4X DDR InfiniBand Switch Module for HP c-Class BladeSystem (1) • HP ProLiant BL460 Server Blades (16) o 2.66-Ghz Intel® Xeon™ processor X5355, quad-core (2 per server blade) o 16GB (8 x 2GB) RAM per server blade o 72GB 15,000-rpm SAS hard drives (2 per server blade) o Emulex Fibre Channel mezzanine (1 per server blade) o HP 4X DDR InfiniBand Mezzanine (1 per server blade) Total system leakage current per branch Total system inrush current per branch (2 mS) Total system weight (includes power and rack) 0 mA 210 A 204 kg (450 lb) Power credentials Total input power Total input VA BTU Total input current Total airflow (CFM) Idle 4484 W 4575 VA 15289 BTU 22 A 270 100% utilization 6801 W 6940 VA 23190 BTU 33.36 A 360 Circuit sizing 8891 W 9072 VA 30318 BTU 43.62 A 530 Configuration scenarios 55

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73

Configuration scenarios 55
HP ProLiant BL465c Server Blades (16)
o
2.8-GHz AMD Opteron™ Model 2220 processor (2 per server blade)
o
8GB (4 x 2GB) RAM per server blade
o
72GB 15,000-rpm SAS hard drives (2 per server blade)
o
QLogic Dual-Port Fibre Channel Mezzanine (1 per server blade)
Total system leakage current per branch
0 mA
Total system inrush current per branch (2 mS)
210 A
Total system weight (includes power and rack)
301 kg (664 lb)
Power credentials
Idle
100% utilization
Circuit sizing
Total input power
2957 W
4624 W
6244 W
Total input VA
3017 VA
4718 VA
6372 VA
BTU
10083 BTU
15767 BTU
21293 BTU
Total input current
14.51 A
22.68 A
30.63 A
Total airflow (CFM)
262
349
516
Total airflow (CMM)
7.408
9.877
14.611
Example maximum configuration
This power summary is based on the following configuration:
HP BladeSystem c7000 Enclosure (1)
HP Virtual Connect Ethernet Modules (2)
HP Virtual Connect Fibre Channel Modules (2)
HP 4X DDR InfiniBand Switch Module for HP c-Class BladeSystem (1)
HP ProLiant BL460 Server Blades (16)
o
2.66-Ghz Intel® Xeon™ processor X5355, quad-core (2 per server blade)
o
16GB (8 x 2GB) RAM per server blade
o
72GB 15,000-rpm SAS hard drives (2 per server blade)
o
Emulex Fibre Channel mezzanine (1 per server blade)
o
HP 4X DDR InfiniBand Mezzanine (1 per server blade)
Total system leakage current per branch
0 mA
Total system inrush current per branch (2 mS)
210 A
Total system weight (includes power and rack)
204 kg (450 lb)
Power credentials
Idle
100% utilization
Circuit sizing
Total input power
4484 W
6801 W
8891 W
Total input VA
4575 VA
6940 VA
9072 VA
BTU
15289 BTU
23190 BTU
30318 BTU
Total input current
22 A
33.36 A
43.62 A
Total airflow (CFM)
270
360
530