Tripp Lite 9PX11K Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and User - Page 15

Submenu, Available settings, Default settings, In/Out settings, On/Off settings, Battery settings

Page 15 highlights

ENGLISH 2. Presentation 8-11kVA US_EN In/Out settings On/Off settings Battery settings Submenu Interrupt time Overload prealarm Redundancy mode Cold start Forced reboot Auto restart Auto start Energy saving Sleep mode Remote command Bypass standby Automatic battery test Low battery warning Restart bat. level Battery charge mode External battery Deep Disch. protect. Available settings If Bypass transfer is enabled, Interrupt time: [10ms] [20ms] Define break duration when transfer on Bypass [10%] ... [102%] Load % when overload alarm occurs [Unitary UPS] [Hot Standby] Force slew rate value to 0.5Hz/s [Enabled] [Disabled] Authorize the product to start on battery power. [Enabled] [Disabled] If mains recover during a shutdown sequence: If set to Enabled, shutdown sequence will complete and wait 10 seconds prior to restart, If set to Disabled, shutdown sequence will not complete and restart will occur immediately. [Enabled] [Disabled] Authorize the product to restart automatically when mains recovers after a complete battery discharge. [Enabled] [Disabled] The UPS automatically starts up as soon as mains power is available (no need topress the button). [Disabled] [100W] ... [1000W] If Enabled, UPS will shutdown after 5 min. of back-up time, if load is less than threshold. [Enabled] [Disabled] If Disabled, LCD and communication will turn OFF immediately after UPS is OFF. If Enabled, LCD and communication stays ON 1h30 min after UPS is OFF. [Enabled] [Disabled] If Enabled, shutdown or restart commands from software are authorized. [Enabled] [Disabled] Define if output is powered from Bypass in Standby mode. In constant charge mode: [No test] [Every day] [Every week] [Every month] In ABM cycling mode : [No test] [Every ABM cycle] [0%] ... [100%] The alarm triggers when the set percentage of battery capacity is reached during back-up time. [0%] ... [100%] If set, automatic restart will occur only when percentage of battery charge is reached. [ABM cycling] [Constant charge] Default settings [10ms] [102%] Unitary UPS [Enabled] [Enabled] [Enabled] [Disabled] [Disabled] [Enabled] [Enabled] [Disabled] [Every ABM cycle] [20%] [0%] [ABM cycling] [Auto detection] [Auto detection] [Manual EBM set.] Using standard EBM, UPS [Manual battery set.] detects automatically the [No battery] number of EBM connected [Yes] [No] [Yes] If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. Warranty void if set to No. Page 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 15
8-11kVA US_EN
ENGLISH
2. Presentation
Submenu
Available settings
Default settings
In/Out settings
Interrupt time
If Bypass transfer is enabled,
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
[10ms]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
Redundancy
mode
[Unitary UPS] [Hot Standby]
Force slew rate value to 0.5Hz/s
Unitary UPS
On/Off settings
Cold start
[Enabled] [Disabled]
Authorize the product to start on
battery power.
[Enabled]
Forced reboot
[Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
[Enabled]
Auto restart
[Enabled] [Disabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
[Enabled]
Auto start
[Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is available
(no need topress the
button).
[Disabled]
Energy saving
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after
5 min. of back-up time, if load is less
than threshold.
[Disabled]
Sleep mode
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
Remote command
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled]
Bypass standby
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
[Disabled]
Battery settings
Automatic battery
test
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[Every ABM cycle]
Low battery
warning
[0%] ... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
[20%]
Restart bat. level
[0%] ... [100%]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[0%]
Battery charge
mode
[ABM cycling] [Constant charge]
[ABM cycling]
External battery
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch.
protect.
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
[Yes]