ENGLISH 8. Troubleshooting The Eaton 9PX is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. • Events are silent status information that are recorded into the Event log. Example = "AC freq in range". • Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking. Some alarms may be announced by a beep every 3 seconds. Example = "Battery low". • Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on the LCD with a specific message box. Example = Out. short circuit. Use the following troubleshooting chart to determine the UPS alarm condition. 8.1 Typical alarms and faults To check the Event log or Fault log : 1. Press any button on the front panel display to activate the menu options. 2. Press the button to select Event log or Fault log. 3. Scroll through the listed events or faults. The following table describes typical conditions. 8-11kVA US_EN Conditions Battery mode Possible cause A utility failure has occurred and the UPS is in Battery mode. LED is On. 1 beep every 10 seconds. Battery low The UPS is in Battery mode and the battery is running low. LED is On. 1 beep every 3 seconds. Action The UPS is powering the equipment with battery power. Prepare your equipment for shutdown. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the "Battery Low" warning may occur before the batteries reach 20% capacity. No battery LED is On. Beep continuous. Battery fault LED is On. Beep continuous. The UPS does not provide the expected backup time. Bypass mode LED is on. Power overload LED is On. Beep continuous. The batteries are disconnected. Verify that all batteries are properly connected. If the condition persists, contact your service representative. The battery test is failed due to bad or disconnected batteries, or the battery minimum voltage is reached in ABM cycling mode. Verify that all batteries are properly connected. Start a new battery test : if the condition persists, contact your service representative. The batteries need charging or service. An overload or a fault has occurred, or a command has been received and the UPS is in Bypass mode Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service representative. Equipment is powered but not protected by the UPS. Check for one of the following alarms: overtemperature, overload or UPS failure. Power requirements exceed the UPS capacity (greater than 100% of nominal; see in table 6 on page 43 for specific output overload ranges). Remove some of the equipment from the UPS. The UPS continues to operate, but may switch to Bypass mode or shut down if the load increases. The alarm resets when the condition becomes inactive. Page 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 39
8-11kVA US_EN
ENGLISH
8. Troubleshooting
The Eaton 9PX is designed for durable, automatic operation and also alerts you whenever potential
operating problems may occur. Usually the alarms shown by the control panel do not mean that the
output power is affected. Instead, they are preventive alarms intended to alert the user.
Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds. Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on
the LCD with a specific message box. Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
8.1
Typical alarms and faults
To check the Event log or Fault log :
1.
Press any button on the front panel display to activate the menu options.
2.
Press the
button to select Event log or Fault log.
3.
Scroll through the listed events or faults.
The following table describes typical conditions.
Conditions
Possible cause
Action
Battery mode
LED is On.
1 beep every 10 seconds.
A utility failure has occurred and
the UPS is in Battery mode.
The UPS is powering the equipment
with battery power. Prepare your
equipment for shutdown.
Battery low
The UPS is in Battery mode and
the battery is running low.
This warning is approximate, and the
actual time to shutdown may vary
significantly.
Depending on the UPS load and
number of Extended Battery Modules
(EBMs), the "Battery Low" warning
may occur before the batteries reach
20% capacity.
LED is On.
1 beep every 3 seconds.
No battery
The batteries are disconnected.
Verify that all batteries are properly
connected.
If the condition persists, contact your
service representative.
LED is On.
Beep continuous.
Battery fault
The battery test is failed due to
bad or disconnected batteries,
or the battery minimum voltage is
reached in ABM cycling mode.
Verify that all batteries are properly
connected. Start a new battery test :
if the condition persists, contact your
service representative.
LED is On.
Beep continuous.
The UPS does not
provide the expected
backup time.
The batteries need charging or
service.
Apply utility power for 48 hours to
charge the batteries. If the condition
persists, contact your service
representative.
Bypass mode
An overload or a fault has
occurred, or a command has been
received and the UPS is in Bypass
mode
Equipment is powered but not
protected by the UPS.
Check for one of the following alarms:
overtemperature, overload or UPS
failure.
LED is on.
Power overload
Power requirements exceed the
UPS capacity (greater than
100% of nominal; see in table 6
on page 43 for specific output
overload ranges).
Remove some of the equipment from
the UPS.
The UPS continues to operate, but
may switch to Bypass mode or shut
down if the load increases.
The alarm resets when the condition
becomes inactive.
LED is On.
Beep continuous.