Tripp Lite 9PX11K Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and User - Page 27
Operation
View all Tripp Lite 9PX11K manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
ENGLISH 5. Operation 5.1 UPS startup and shutdown If you ordered a HotSwap MBP, refer to the specific user manual to check the startup sequence of the UPS with the MBP. Starting the UPS Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm. To start the UPS: 1. Verify that the EBM are connected to the UPS. See "Connecting the EBM(s)" on page 18. Check that the battery circuit breaker is switched to the "I" position (On). 2. Verify that the UPS terminal blocks are connected to AC source. 3. Set the upstream circuit breaker (not provided) to the "I" position (On) to switch on the utility power. The UPS front panel display illuminates and shows EATON logo. 4. Verify that the UPS status screen shows , press to start. 5. Press the button on the UPS front panel for at least 3 seconds. The UPS front panel display changes status to "UPS starting...". 6. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before conti- nuing. See "Troubleshooting" on page 39. If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. 7. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and powering the output. The UPS should be in Online mode. The EBM charge to 90% capacity in less than 3 hours. However, Eaton recommends that the batteries charge for 48 hours after installation or long-term storage. Starting the UPS on Battery Before using this feature, the UPS must have been powered by utility power with output enabled at least once. Battery start can be disabled. See Coldstart setting in user settings on page 14. To start the UPS on battery: 1. Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of "UPS starting...". The UPS cycles through Standby mode to Battery mode. The The UPS supplies power to your equipment. indicator illuminates solid. 2. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See "Troubleshooting" on page 39. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. UPS shutdown To shut down the UPS: 1. Press the button on the UPS front panel. The UPS transfers to Standby mode. 2. Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power. 8-11kVA US_EN Page 27