Tripp Lite 9PX11K Eaton 9PX 8000 9PX 11000 9PX EBM 240V Installation and User - Page 44
Remote On/Off
View all Tripp Lite 9PX11K manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 44 highlights
9. Specifications Agency markings Operating temperature Storage temperature Transit temperature Relative humidity Operating altitude Transit altitude Audible noise CE / cULus / NOM 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude Note: thermal protection switches load to Bypass in case of overheating. 0 to 40°C (32 to 104°F) with batteries -15 to 60°C (5 to 140°F) without batteries -25 to 55°C (-13 to 130°F) 0 to 95% no condensing Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m Up to 10,000 meters (32,808 ft) above sea level < 48 dBA at 1 meter typical for 8kVA models < 50 dBA at 1 meter typical for 11kVA models Table 9. Battery Rack / Tower configuration Type Monitoring Battery port EBM battery cable length EBMs 9PXEBM240RT: 240Vdc Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F). Lifetime is reduced above 30 °C. Advanced monitoring for earlier failure detection and warning External three-pole SBS75G White connector on Power Module for connection to EBM 40cm (15.7in) Table 10. Communication options Communication bay Compatible connectivity cards Communication ports Relay output contacts Remote On/Off Remote Power Off (1) available independent communication bay for connectivity cards Network-MS Modbus-MS Relay-MS RS-232 (DB9): 1200-19200 bps USB: 19200 bps (4) relay outputs (normally open or normally closed) 2 pins jumper (normally open) 3 pins jumper (normally open or normally closed) Page 44 8-11kVA US_EN