Connect correctly the Input/Output
View all Tripp Lite 9PX11K manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 40 highlights
8. Troubleshooting UPS overtemperature LED is On. 1 beep every 3 seconds. The UPS internal temperature is too high or a fan has failed. At the warning level, the UPS generates the alarm but remains in the current operating state. If the temperature rises another 10°C, the UPS transfers to Bypass mode or shuts down if Bypass is unusable. If the UPS transferred to Bypass mode, the UPS will return to normal operation when the temperature drops 5°C below the warning level. If the condition persists, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. Restart the UPS. If the condition continues to persist, contact your service representative. The UPS does not start. The input source is not connected Check the input connections. correctly. Input bad wiring / Output bad wiring The Remote Power Off (RPO) switch is active or the RPO connector is missing. Input/Output cables are not connected to the correct terminal blocks. If the UPS Status menu displays the "Remote Power Off" notice, inactivate the RPO input. Connect correctly the Input/Output cables. Led is On. Beep continuous. MBP disconnected The HotSwap MBP is no more connected to the UPS. If the HotSwap MBP is connected to the UPS, check that the detection connector is correctly plugged. Page 40 8-11kVA US_EN