Foundation H1 Bus Default probe setting 10:1. Use the Fluke 10:1 probe. 1 Connect the red probe to test tool input A 2 Connect the probe ground lead to the H1 bus + 3 Connect the probe tip to the H1 bus - DATA + DATA - Figure 41. Foundation H1 Bus Measurement Connections 6 Using The Bushealth Function Input Connections and Tested Signals Table 7. Foundation H1 Bus Tested Signal Properties Signal V-Level Bias V-Level Data Rise Fall Jitter Signal Dist. Noise-HF Noise Noise-LF Description Bias voltage level Peak-peak voltage Bit width Rise time as % of bit width Fall time as % of bit width Jitter distortion Signal distortion High Frequency noise >39.1 kHz Mid Frequency noise 7.8 ....39.1 kHz Low Frequency noise < 7.8 kHz Note The bus normally has continuous data traffic. 75