PDU Critical Overcurrent L2 Phase: Number code 211402, Type Code = 2 PDU, Identification = 114
![]() |
View all HP 11kVA 400 Volt IEC309 16A 3-Phase Input 18xC13/3xC19 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 111 highlights
Maintenance and Alarms Figure 56 provides an example of a Type Code 2 system alarm number code. PDU Critical Overcurrent L2 Phase: Number code 211402 Type Code = 2 (PDU) Identification = 114 Index code = 02 2 11 4 02 Figure 56. Example Type 2 System Alarm Number Code Table 12 lists PDU and User alarms and events. Table 12. PDU and User Alarms and Events Identification and Type Code Index Code Alarm or Event Description 2 201000 2 201100 2 202000 Dry Contact 1 Active Dry Contact 1 Not Active Dry Contact 1 Open The signal for Dry Contact 1 is active. The signal for Dry Contact 1 is not active. Dry Contact 1 is open. 2 202100 2 203000 2 203100 2 204000 2 204100 2 205000 2 205100 2 208000 2 208100 2 206000 Dry Contact 1 Closed Dry Contact 1 is closed. Dry Contact 2 Active The signal for Dry Contact 2 is active. Dry Contact 2 Not Active The signal for Dry Contact 2 is not active. Dry Contact 2 Open Dry Contact 2 is open. Dry Contact 2 Closed Dry Contact 2 is closed. Sensor Probe Communication Failure Cleared Sensor Probe communication failure is cleared Sensor Probe Communication Failure Sensor probe communication failure detected Sensor Probe Not Connected Sensor probe not connected since firmware startup Sensor Probe Connected Sensor probe connected at least once since firmware startup Humidity No Threshold No humidity threshold has been triggered. 2 206100 2 206200 2 206300 2 206400 2 207000 2 207100 2 207200 2 207300 Humidity Warning Low Threshold Humidity Critical Low Threshold Humidity Warning High Threshold Humidity Critical High Threshold Temperature No Threshold Temperature Warning Low Threshold Temperature Critical Low Threshold Temperature Warning High Threshold The humidity level reading is less than the value configured as the low humidity warning threshold. The humidity level reading is less than the value configured as the low humidity critical threshold. The humidity level reading is greater than the value configured as the high humidity warning threshold. The humidity level reading is greater than the value configured as the high humidity critical threshold. No temperature threshold has been triggered. The temperature level reading is less than the value configured as the low temperature warning threshold. The temperature level reading is less than the value configured as the low temperature critical threshold. The temperature level reading is greater than the value configured as the high temperature warning threshold. HP Monitored PDU User's Guide P-164000281-Rev 1 105
![](/manual_guide/products/hewlettpackard-36kva-hp-monitored-power-distribution-unit-user-guide-9f24a2e/111.png)