Overcurrent Protection
View all HP 11kVA 400 Volt IEC309 16A 3-Phase Input 18xC13/3xC19 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 117 highlights
Specifications Table 17. Electrical Ratings (Continued) Model Input Voltage D9N56A D9N57A D9N58A D9N59A D9N60A D9N61A D9N62A D9N63A 200-240V/346-415V wye 200-240V/346-415V wye 208V delta 208V delta 200-240V/346-415V wye 200-240V/346-415V wye 200-240V/346-415V wye 277/480V wye Output Voltage 200-240V 200-240V 200-240V 200-240V 200-240V 200-240V 200-240V 277V Input Current (A) 32 16 40 48 32 24 24 24 Capacity (VA) 22080 11040 14410 17293 22080 16560 16560 19944 Table 18. Output Current Ratings (All PDU Models) Outlets IEC IEC 60320 C13 10A IEC 60320 C19 16A NEMA 5-20R 16A RF-203P-HP 277V (LS26) 15A UL/CSA 15A 16A 16A 15A Overcurrent Protection Table 19 lists the overcurrent protection requirements for the PDU models with outlet groups protected by circuit breakers. Table 19. Overcurrent Protection Model Breaker Qty D9N43A 2 D9N44A 2 D9N45A 0 D9N46A 0 D9N47A 2 D9N48A 2 D9N49A 3 D9N50A 2 D9N51A 3 D9N52A 0 D9N53A 3 D9N54A 6 D9N55A 0 D9N56A 6 D9N57A 0 D9N58A 6 D9N59A 6 D9N60A 6 D9N61A 6 Breaker Type SEE NOTE SP DP - - DP SP DP SP DP - DP DP - SP - DP DP SP SP Breaker Rating (A) 20A 20A - - 20A 16A 20A 16A 20A - 20A 20A - 16A - 20A 20A 16A 20A Notes UL 489 UL 489 - - UL 489 IEC/EN 60934 UL 489 IEC/EN 60934 UL 489 - UL 489 UL 489 - IEC/EN 60934 - UL 489 UL 489 IEC/EN 60934 UL 489 HP Monitored PDU User's Guide P-164000281-Rev 1 111