HP R1500 HP UPS R3000 User Guide - Page 46
Specifications, UPS physical specifications
![]() |
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 46 highlights
Specifications UPS physical specifications Parameter Height Depth Width Weight Value 8.9 cm (3.5 in) 62.2 cm (25 in) 44.1 cm (17.5 in) 37 kg (82 lb) ERM physical specifications Parameter Height Depth Width Weight Value 8.9 cm (3.5 in) 34.3 cm (13.5 in) 44.5 cm (17.5 in) 45 kg (100 lb) UPS input specifications NOTE: An asterisk (*) indicates the default setting. UPS model R3000 NA R3000j JPN R3000h NA R3000h JPN R3000 INTL Utility voltage frequency (Hz) 50/60 50/60 50/60 50/60 50/60 Available settings utility voltage (VAC) 100, 110, 120*, 127 100*, 110, 120, 127 200/208*1, 220, 230, 240 200/208*1, 220, 230, 240 200/208, 220, 230*, 240 Branch circuit rating (A) 30 30 20 20 16 Line cord Nondetachable power cord with NEMA L5-30 plug Nondetachable power cord with NEMA L5-30 plug Nondetachable power cord with NEMA L6-20 plug Nondetachable power cord with NEMA L6-20 plug Detachable power cord with country-specific plug Specifications 46