HP R1500 HP UPS R3000 User Guide - Page 48

Output tolerance specifications, Battery specifications, Battery runtime

Page 48 highlights

Configuration setting (VAC) 208 230 240 Available nominal output voltage (VAC) 208 230 240 Output tolerance specifications Source of power Utility power (nominal range) Battery power Regulation -10% to +6% of nominal output voltage rating (within the guidelines of the Computer Business Equipment Manufacturers Association) ±5% of nominal output voltage rating Output feature specifications Feature Online efficiency Voltage wave shape Surge suppression Noise filtering Specification 94% nominal input voltage Sine wave; 5% THD with typical PFC load High-energy 6500 A peak MOVs and line filter for normal and common mode use Battery specifications Feature Type Voltage Charging Specification 12 V, 5 AH, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a 3-5 year service life at 25°C (77°F). The battery modules have a battery string voltage of 120 V. Complete charge takes no more than 24 hours. After approximately 4 hours, the batteries reach 90% charge at default nominal utility voltage and no load. Battery runtime Load, percent 20 50 80 100 Estimated battery runtime 40 minutes 12 minutes 6.5 minutes 5 minutes Runtime with one ERM 120 minutes 45 minutes 30 minutes 20 minutes Runtime with two ERMs 250 minutes 100 minutes 60 minutes 40 minutes Specifications 48

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65

Specifications 48
Configuration setting (VAC)
Available nominal output voltage (VAC)
208
208
230
230
240
240
Output tolerance specifications
Source of power
Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer
Business Equipment Manufacturers
Association)
Battery power
±5% of nominal output voltage rating
Output feature specifications
Feature
Specification
Online efficiency
94% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load
Surge suppression
High-energy 6500 A peak
Noise filtering
MOVs and line filter for normal and common mode
use
Battery specifications
Feature
Specification
Type
12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at
25
°
C (77
°
F).
Voltage
The battery modules have a battery string voltage of 120 V.
Charging
Complete charge takes no more than 24 hours. After
approximately 4 hours, the batteries reach 90% charge at
default nominal utility voltage and no load.
Battery runtime
Load, percent
Estimated battery
runtime
Runtime with one ERM
Runtime with two ERMs
20
40 minutes
120 minutes
250 minutes
50
12 minutes
45 minutes
100 minutes
80
6.5 minutes
30 minutes
60 minutes
100
5 minutes
20 minutes