Verify that all the terminal blocks and jumpers are installed in each UPS.
View all HP RP36000/3 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 85 highlights
o Set the card for the middle UPS(s) to Pins 2 and 3. 4. Install the Parallel UPS Card into an open X-Slot on the rear of the UPS. 5. Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled. The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on page 78)" . 6. Verify that all the terminal blocks and jumpers are installed in each UPS. 7. Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting the card OUT port on one UPS to the card IN port on the next UPS. Maintenance 85
Maintenance 85
o
Set the card for the middle UPS(s) to Pins 2 and 3.
4.
Install the Parallel UPS Card into an open X-Slot on the rear of the UPS.
5.
Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled.
The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on
the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on
page
78
)" .
6.
Verify that all the terminal blocks and jumpers are installed in each UPS.
7.
Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting
the card OUT port on one UPS to the card IN port on the next UPS.