HP RP36000/3 HP 3 Phase UPS User Guide - Page 94
Troubleshooting, LED and audible alarm troubleshooting
View all HP RP36000/3 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 94 highlights
Troubleshooting LED and audible alarm troubleshooting This UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems might occur. Usually the alarms shown on the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert you of a possible condition. The following table describes typical alarms and conditions. If an alarm appears with a service code, contact HP technical support ("HP contact information" on page 107). To check the Event Log for a list of active alarms: 1. Press any button on the front panel display to activate the menu options. 2. Press the down arrow button until EVENT LOG displays. 3. Press the right arrow button to display the list of alarms and conditions. Alarm On Battery Power On Auto-Bypass LED LED LED LED Audible alarm Condition On On On On On Flashing On Flashing UPS is in Normal mode (on page 65). A new message is active. On-1 beep On Battery ("UPS is every 5 seconds on battery" on page 100) On-Continuous Battery Low for 10 seconds ("Battery low condition" on page 96) On-1 beep Battery Breaker (on every 3 seconds page 95) On-1 beep On Bypass ("UPS is every 3 seconds on bypass" on page 100) On-1 beep every 1 seconds Bypass Unavailable ("Bypass is unavailable" on page 96) On-1 beep every 3 seconds Battery Connection ("Battery connection condition" on page 96) Troubleshooting 94