HP RP36000/3 HP 3 Phase UPS User Guide - Page 98
Protected equipment is not on, Overload condition, Overtemperature condition, Redundancy loss due
![]() |
View all HP RP36000/3 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 98 highlights
4. To supply power to the connected equipment, power up the UPS. o Standalone UPS configuration-See "Powering up the standalone UPS (on page 25)." o Parallel UPS configuration-See "Powering up the parallel system (on page 39)." Protected equipment is not on Possible cause: The UPS is operating normally, but some or all of the protected equipment is not on. Action: • Be sure that the equipment is plugged into the UPS receptacles. • Be sure that the output circuit breaker is in the Off position. Overload condition Possible cause: Power requirements exceed the UPS capacity. For output overload ranges, see "UPS output specifications (on page 103)." Action: Remove one or more load devices to reduce the power requirements.The UPS continues to operate, but might switch to Auto-Bypass mode (on page 66) if the load increases. The alarm resets when the conditions becomes inactive. Overtemperature condition Possible cause: The UPS internal temperature is too high, or a fan has failed. Action: 1. Power down the UPS. o Standalone UPS configuration-See "Powering down the standalone UPS (on page 72)." o Individual UPS in a parallel configuration-See "Powering down an individual paralleled UPS (on page 72)." o Parallel UPS configuration-See "Powering down the parallel system (on page 73)." 2. Allow the UPS to cool: a. Clear vents and remove any heat sources. b. Be sure that the that the airflow around the UPS is not restricted. 3. Wait at least 5 minutes and restart the UPS. 4. If the condition persists, contact an HP authorized service representative. Redundancy loss due to overload Possible cause: The specified power rating of the parallel system has been exceeded. Action: The load is supported, but the system lacks redundant protection while the overload condition persists. Troubleshooting 98
![](/manual_guide/products/hewlettpackard-rp360003-hp-3-phase-ups-user-guide-84ca70d/98.png)