Modbus Configuration, To view and con the Modbus Server:
View all Lantronix XPort Pro manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 102 highlights
11: Modbus Modbus Configuration This web page shows the current negotiated Modbus settings and allows configuration changes. To view and configure the Modbus Server: 1. Click Modbus on the menu bar and then click Configuration at the top of the page. The Modbus Configuration page appears. Figure 11-6 Modbus Configuration 2. Enter or modify the following settings: Table 11-7 Modbus Configuration Modbus Configuration Settings TCP Server State Additional TCP Server Port Response Timeout RSS Trace Input Description If On, the Modbus server is active on TCP 502. If present, is used in addition to TCP port 502. The number of milliseconds to wait for a response on the serial side. The device returns exception code 11 to the network master controller if the slave serial device fails to reply within this time out. If On, each PDU received on the Modbus serial line creates a non-persistent descriptive item in the RSS feed. 3. Click Submit. The changes take effect immediately. Note: The serial line protocol must also be configured for Modbus, in addition to configuring the Modbus server. See Chapter 6: Line and Tunnel Settings on page 32 for details. XPort Pro User Guide 102