Operation (continued) Display Information-Bypass Mode When operating in Bypass Mode, you will see the following sequence display: LOAD LEVEL 00.00KW / 000% LOAD LEVEL 00.00KVA / 000% INPUT VOLTAGE 000V / 00.0Hz BYPASS VOLTAGE 000V / 00.0Hz OUTPUT VOLTAGE 000V / 00.0Hz BATTERY CAPACITY 000V / 000% REMAINING TIME 0000 MINUTES ON-LINE 10KVA V00 CV01 UPS Fault Shutdown Messages CONDITION +BUS >450V Load 100%: +BUS 450V Load
23
Operation (continued)
Display Information-Bypass Mode
When operating in Bypass Mode, you will see the following sequence display:
UPS Fault Shutdown Messages
CONDITION
LCD DISPLAY MESSAGES
+BUS >450V
+ DC BUS HIGH
SHUTDOWN
Load <100%: +BUS < 320V
Load >100%: +BUS <290V
+ DC BUS LOW
SHUTDOWN
-BUS >450V
- DC BUS HIGH
SHUTDOWN
Load <100%: -BUS <320V
Load >100%: -BUS <290V
- DC BUS LOW
SHUTDOWN
BUS Voltage Over 500
BUS OVP FAIL
SHUTDOWN
Output Short
OUTPUT SHORT
SHUTDOWN
UPS Over Temperature
OVER TEMPERATURE
SHUTDOWN
Ouput SCR Open Failure
OUTPUT SCR FAIL
SHUTDOWN
Output Overload
OVERLOAD
SHUTDOWN
Bypass SCR Short
BYPASS SCR FAIL
SHUTDOWN
Input SCR Rectifier Failure
RECTIFIER FAIL
SHUTDOWN
Inverter Output Voltage Failure
INVERTER
SHUTDOWN
Input Fuse Open
I / P FUSE BROKEN
SHUTDOWN
Output Fuse Open
O / P FUSE BROKEN
SHUTDOWN
Parallel ID Lost
PARALLEL FAULT
SHUTDOWN
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
ON-LINE 10KVA
V00
CV01
REMAINING TIME
0000 MINUTES