Tripp Lite SU8000RT3U Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897 - Page 24

On Battery Alarm, Overload Messages, Bypass Messages

Page 24 highlights

Operation (continued) On Battery Alarm When in the On Battery mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment. If its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it will beep twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously. To silence the On Battery Alarm, press the "ON/MUTE" button. Overload Messages When the UPS detects an output overload, its LCD will switch to the following display: OVERLOAD! LOAD = XXX% X.XXKW The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows: Overload Condition 106% - 125% 126% - 150% >150% Countdown Duration 1 minute 30 seconds Immediate Bypass Messages While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in Bypass Mode. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal. BYPASS VOLTAGE CONDITIONS LCD DISPLAY MESSAGES >15% Higher Than Nominal BYPS OUT OF VOLT XXXV / XX.X HZ >20% Lower Than Nominal BYPS OUT OF VOLT XXXV / XX.X HZ 24 201102160 93-2897.indb 24 3/30/2011 9:30:52 AM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104

24
Operation (continued)
On Battery Alarm
When in the On Battery mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment. If
its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it will beep
twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously.
To silence the On Battery Alarm, press the “ON/MUTE” button.
Overload Messages
When the UPS detects an output overload, its LCD will switch to the following display:
Bypass Messages
While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide
battery backup in Bypass Mode.
If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its
LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and
its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass Mode to
protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
Overload Condition
Countdown Duration
106% - 125%
1 minute
126% - 150%
30 seconds
>150%
Immediate
>15% Higher
Than Nominal
>20% Lower
Than Nominal
BYPASS VOLTAGE
CONDITIONS
LCD DISPLAY
MESSAGES
BYPS OUT OF VOLT
XXXV / XX.X HZ
BYPS OUT OF VOLT
XXXV / XX.X HZ
OVERLOAD!
LOAD = XXX% X.XXKW
201102160
93-2897.indb
24
3/30/2011
9:30:52 AM