Environmental, AC Power Supply Unit Requirements
View all Dell Force10 E600i manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 56 highlights
www.dell.com | support.dell.com Environmental Parameter Operating Temperature Maximum altitude Relative humidity Non-operating Temperature Maximum altitude Relative humidity Specifications 32° to 104°F (0° to 40°C) No performance degradation to 10,000 feet (3,048 meters) 5 to 85 percent, noncondensing -40° to 158°F (-40° to 70°C) 15,000 feet (4,572 meters) 5 to 95 percent, noncondensing AC Power Supply Unit Requirements Parameter Specifications Nominal Input Voltage 120 - 240 VAC 50/60 Hz Maximum AC Power Supply Input 16 A @ 100 VAC per module 12 A @ 200 VAC per module Maximum Thermal Output (3,172 W) Maximum Thermal Output (2,906 W) 10,822 BTU/hour at 100/120 VAC 9,914 BTU/hour at 200/240 VAC Maximum AC Supply Input Current (based on 2500 W output for 100/120V and 200/240V lines.) 11.6 A @ 100 VAC 9.7 A @ 120 VAC 8.0 A @ 200 VAC 6.7 A @ 240 VAC Maximum System Power Input 3.5 KVA @ 100/120 VAC 3.2 KVA @ 220/240 VAC Maximum Power Consumption 3,422 W at 100/120 VAC 3,156 W at 200/240 VAC Nominal Input Voltage Maximum System Power Input Parameter Maximum DC PEM Input Current System Input Voltage 100 - 120 VAC Requires a minimum of 3 Power Supplies Installed 200 - 240 VAC Requires a minimum of 2 Power Supplies Installed 4.80 KVA @ 100 VAC 4.60 KVA @ 220 VAC Specifications 75A 2800W (9600 BTU/hour) -48 to -60 Vdc 56 | System Specifications