HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 26
PDCA Assembly for Options 6 and 7 4-Wire Unit Shown, Plug in-line connector not shown
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
Electrical Specifications Power Options • To verify the proper wiring for a 4-wire PDCA, use a DVM to measure the voltage at the in-line connector. Voltage should read 200 - 240 Vac phase-to-phase as measured between the connector pins as follows: L1 to L2, L2 to L3, L1 to L3. • To verify the proper wiring for a 5-wire PDCA, use a DVM to measure the voltage at the connector. Voltage should read 200 - 240 Vac phase-to-neutral as measured between the connector pins as follows: L1 to N, L2 to N, L3 to N. Figure 3-2 PDCA Assembly for Options 6 and 7 (4-Wire Unit Shown) Measurement points L3-L1 L2-L3 L1-L2 60SP049A 8/17/01 Plug (in-line connector not shown) 18 Chapter 3
Chapter 3
Electrical Specifications
Power Options
18
•
To verify the proper wiring for a 4-wire PDCA, use a DVM to measure the voltage at the in-line connector.
Voltage should read 200 - 240 Vac phase-to-phase as measured between the connector pins as follows: L1
to L2, L2 to L3, L1 to L3.
•
To verify the proper wiring for a 5-wire PDCA, use a DVM to measure the voltage at the connector.
Voltage should read 200 - 240 Vac phase-to-neutral as measured between the connector pins as follows: L1
to N, L2 to N, L3 to N.
Figure 3-2
PDCA Assembly for Options 6 and 7 (4-Wire Unit Shown)
8/17/01
60SP049A
L3-L1
L2-L3
L1-L2
Plug (in-line connector not shown)
Measurement points