HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 56

Cooling Requirements, Basic Air Conditioning Equipment Requirements, Air filtration

Page 56 highlights

Facility Guidelines Electrical and Environmental Guidelines • Ensure a minimum ceiling height of 12 inches between the top of the server and the ceiling. Ensure all ceiling clips are in place. Cooling Requirements Air conditioning equipment requirements and recommendations are described in the following sections. Basic Air Conditioning Equipment Requirements The cooling capacity of the installed air conditioning equipment for the computer room should be sufficient to offset the computer equipment dissipation loads, as well as any space envelope heat gain. This equipment should include: • Air filtration • Cooling or dehumidification • Humidification • Reheating • Air distribution • System controls adequate to maintain the computer room within the operating ranges listed in Table 5-1. 48 Chapter 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106

Chapter 5
Facility Guidelines
Electrical and Environmental Guidelines
48
Ensure a minimum ceiling height of 12 inches between the top of the server and the ceiling. Ensure all
ceiling clips are in place.
Cooling Requirements
Air conditioning equipment requirements and recommendations are described in the following sections.
Basic Air Conditioning Equipment Requirements
The cooling capacity of the installed air conditioning
equipment for the computer room should be sufficient to offset the computer equipment dissipation loads, as
well as any space envelope heat gain. This equipment should include:
Air filtration
Cooling or dehumidification
Humidification
Reheating
Air distribution
System controls adequate to maintain the computer room within the operating ranges listed in Table 5-1.