HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 42

Table 4-3, Typical hp Integrity Superdome Configurations, Memory, Typical, Watts, Cooling, BTU/Hr.

Page 42 highlights

Environmental Requirements Power Dissipation Table 4-3 Typical hp Integrity Superdome Configurations Cell Memory IO Typical (Watts) Cooling (BTU/Hr.) Breaker Power (Watts)a 3-Pole Breaker Size (Amperes)a,b 4-Pole Breaker Size (Amperes)a,c,d 8 32 4 9790 33406 12335 40 25 8 16 2 8450 28834 10647 40 25 8 8 4 8680 29619 10937 40 25 8 8 2 8170 27878 10294 35 20 8 4 4 8400 28663 10584 35 20 8 4 2 7700 26275 9702 35 20 6 16 4 7370 25149 9286 35 20 6 16 2 6660 22726 8392 30 20 6 8 4 7010 23920 8833 30 20 6 8 2 6300 21497 7938 30 20 6 4 4 6800 23204 8568 30 20 6 4 2 6100 20815 7686 30 20 4 16 4 5880 20064 7409 30 20 4 16 2 5170 17642 6514 30 20 4 8 4 5340 18222 6728 30 20 4 8 2 4630 15799 5834 25 20 4 4 4 5200 17744 6552 25 20 4 4 2 4500 15355 5670 25 20 2 16 2 3800 12967 4788 20 20 2 8 2 3500 11943 4410 20 20 2 4 2 3400 11602 4284 20 20 a. These numbers are valid only for the specific configurations shown. Any upgrades may require a change to the breaker size. A 5-wire source utilizes a 4 pole breaker and a 4-wire source utilizes a 3 pole breaker. The PE (Protective Earth) ground wire is not switched. b. An input power source supplied from a 3-pole plus protective earth (PE), 4-wire system will always be wired as 240 volts phase-to-phase, no neutral or common, plus a PE ground. Three phase input voltage (240VAC) to the equipment is connected phase-to-phase. Examples of 4 wire: 200-volt phase-to-phase, 208-volt phase-to-phase, 220-volt phase-to-phase, 230-volt phase-to-phase, 240-volt phase-to-phase. 34 Chapter 4

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106

Chapter 4
Environmental Requirements
Power Dissipation
34
Table 4-3
Typical hp Integrity Superdome Configurations
Cell
Memory
IO
Typical
(Watts)
Cooling
(BTU/Hr.)
Breaker
Power
(Watts)
a
a. These numbers are valid only for the specific configurations shown. Any upgrades may require
a change to the breaker size. A 5-wire source utilizes a 4 pole breaker and a 4-wire source
utilizes a 3 pole breaker.
The PE (Protective Earth) ground wire is not switched.
3-Pole Breaker
Size
(Amperes)
a,b
b.
An input power source supplied from a 3-pole plus protective earth (PE), 4-wire system will
always be wired as 240 volts phase-to-phase, no neutral or common, plus a PE ground. Three
phase input voltage (240VAC) to the equipment is connected phase-to-phase. Examples of 4
wire: 200-volt phase-to-phase, 208-volt phase-to-phase, 220-volt phase-to-phase, 230-volt
phase-to-phase, 240-volt phase-to-phase.
4-Pole Breaker
Size
(Amperes)
a,c,d
8
32
4
9790
33406
12335
40
25
8
16
2
8450
28834
10647
40
25
8
8
4
8680
29619
10937
40
25
8
8
2
8170
27878
10294
35
20
8
4
4
8400
28663
10584
35
20
8
4
2
7700
26275
9702
35
20
6
16
4
7370
25149
9286
35
20
6
16
2
6660
22726
8392
30
20
6
8
4
7010
23920
8833
30
20
6
8
2
6300
21497
7938
30
20
6
4
4
6800
23204
8568
30
20
6
4
2
6100
20815
7686
30
20
4
16
4
5880
20064
7409
30
20
4
16
2
5170
17642
6514
30
20
4
8
4
5340
18222
6728
30
20
4
8
2
4630
15799
5834
25
20
4
4
4
5200
17744
6552
25
20
4
4
2
4500
15355
5670
25
20
2
16
2
3800
12967
4788
20
20
2
8
2
3500
11943
4410
20
20
2
4
2
3400
11602
4284
20
20