HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 31
Cable Preparation Detail, Step 5.
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 31 highlights
Electrical Specifications Power Options Step 5. Using the five screws retained from the removal procedure, replace the bottom panel on the PDCA. Refer to Figure 3-5 on page 21 for panel installation details. Step 6. To verify the proper wiring to a 4-wire PDCA, use a DVM to measure the voltage at the test points. Voltage should read 200 - 240 Vac phase-to-phase as measured between the test points as follows: L1 to L2, L2 to L3, L1 to L3. IMPORTANT In some electrical distributions around the world, it is possible to measure 415 VAC phase-to-phase. Ensure that your DVM is capable of measuring AC voltages of at least 500VAC. A number of 5-wire power distribution systems may have phase-to-phase voltages in excess of 400VAC. Many hand-held volt meters are limited to 300VAC. To verify the proper wiring to a 5-wire PDCA, use a DVM to measure the voltage at the test points. Voltage should read 200-240VAC phase-to-neutral, as measured between the test points as follows: L1 to N, L2 to N, L3 to N. Figure 3-7 Cable Preparation Detail 0.6 in 1.5 cm 7.0 in 18 cm 4.5 in 11.5 cm 0.6 in 1.5 cm 60 Ground Wire GN/YW NOTE Dimensions shown are for a cable strain relief without an extension nipple. If an extension nipple is used, then the cable jacket must removed accordingly. Chapter 3 23