HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 27

Four-Wire In-Line Connector A4660A Opt 401, Cable Removal

Page 27 highlights

Electrical Specifications Power Options IMPORTANT Ensure that your DVM is capable of measuring AC voltages of at least 500VAC. A number of 5-wire power distribution systems may have phase-to-phase voltages in excess of 400VAC. Many hand-held volt meters are limited to 300VAC. Figure 3-3 Four-Wire In-Line Connector (A4660A Opt 401) L2 PE Figure 3-4 L1 L3 60SP048A 11/8/00 Five-Wire In-Line Connector (A4660A Opt 501) L3 N L2 L1 PE 60SP047A 11/8/00 Cable Removal Some installations may either require or desire that the cabinet(s) be hardwired in lieu of using the standard plugs and connectors provided. In these cases, it is necessary to remove the installed power cable from the PDCA. The following procedures are used to remove and replace the existing power cable. Chapter 3 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106

Chapter 3
Electrical Specifications
Power Options
19
IMPORTANT
Ensure that your DVM is capable of measuring AC voltages of at least 500VAC. A number of
5-wire power distribution systems may have phase-to-phase voltages in excess of 400VAC.
Many hand-held volt meters are limited to 300VAC.
Figure 3-3
Four-Wire In-Line Connector (A4660A Opt 401)
Figure 3-4
Five-Wire In-Line Connector (A4660A Opt 501)
Cable Removal
Some installations may either require or desire that the cabinet(s) be hardwired in lieu of using the standard
plugs and connectors provided. In these cases, it is necessary to remove the installed power cable from the
PDCA. The following procedures are used to remove and replace the existing power cable.
11/8/00
60SP048A
L3
L1
L2
PE
11/8/00
60SP047A
PE
L1
L2
L3
N