System Power Requirements, Table 3-3, Power Requirements without Support Management Station
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 34 highlights
Electrical Specifications System Power Requirements System Power Requirements Table 3-3 and Table 3-4 list the AC power requirements for a hp Integrity Superdome and hp 9000 Superdome systems. These tables provide information to help determine the amount of AC power needed for your computer room. Table 3-3 Power Requirements (without Support Management Station) Requirements Value Comments Nominal input voltage 200/208/220/230/240 (VAC rms) Input voltage range (minimum - maximum) 200 - 240 (VAC rms) Frequency range (minimum - maximum) Number of phases Maximum inrush current Product Label maximum current, three-phase, four-wire Product Label maximum current, three-phase, five-wire Power factor correction Ground leakage current (mA) 50/60 (Hz) 3 90 (A peak) 44 (A rms) 24 (A rms) 0.95 minimum > 3.5 ma Autoselecting (measured at input terminals) Per phase at 200-240VAC Per phase at 200-240VAC See WARNING below. WARNING Beware of shock hazard. When connecting or removing input power wiring, always connect the ground wire first and disconnect it wire last. 26 Chapter 3