HP Integrity Superdome SX1000 Site Preparation Guide, Fifth Edition - HP Integ - Page 36
I/O Expansion Cabinet Power Requirements, Table 3-5, Management Station
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Electrical Specifications I/O Expansion Cabinet Power Requirements I/O Expansion Cabinet Power Requirements The I/O expansion cabinet requires a single phase 200-240VAC input. Table 3-5 lists the AC power requirements for the I/O expansion cabinet. NOTE Table 3-5 The IOX accommodates two AC inputs for redundancy I/O Expansion Cabinet Power Requirements (without Support Management Station) Requirements Nominal input voltage Input voltage range (minimum-maximum) Frequency range (minimum-maximum) Number of phases Marked Electrical input current Maximum inrush current Power factor correction Value 200/208/220/230/240 (VAC rms) 200-240 (VAC rms) 50/60 (Hz) 1 16A 60 max (A peak) 0.95 minimum Table 3-6 I/O Expansion Cabinet Component Power Requirements Power Required (50 - 60 Hz) VA Fully configured cabinet I/O cardcage ICE 3200 500 600 28 Chapter 3