LG ARUB115BT2 Installation Manual - Page 32

Refrigerant piping system

Page 32 highlights

Refrigerant piping installation Refrigerant piping system Example : 3 outdoor units, 4 HR units and 11 indoor units Outdoor unit Y branch HR unit Indoor unit Slave 1 A2 Master A1 H h F2 E F1 E2 E1 A B1 D1 a D2 b B C1 C1 c D3 d B2 "a" C3 C2 g D4 C2 D7 f e D C3 i "b" C4 jk D9 D8 * D10 D6 D5 I Case 1 ("a") : Maximum height is 15m(236ft) if you install with Y branch. I Case 2 ("b") : Height is zero(0) m in HR unit serial connector. WARNING * : Serial connection of HR units : Capacity sum of indoor units ≤ 160kBtu/hr • Refer to the HR unit PCB part for the valve group control setting. • It is recommended that difference in pipe lengths between an HR unit and indoor units, for example difference in length of a, b, c, and d, be minimized. The larger difference in pipe lengths, the more different performance between indoor units. • Piping length from outdoor branch to outdoor unit ≤ 10m(33ft), equivalent length : max 13m(43ft) (For 18 HP or more) ❈ If the large capacity indoor units(5~10 HP, using over Ø15.88(5/8) / Ø9.52(3/8))are installed, it should use Valve Group setting. 32 Outdoor Unit

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83

32
Outdoor Unit
32
Outdoor Unit
Refrigerant piping installation
Refrigerant piping system
Example : 3 outdoor units, 4 HR units and 11 indoor units
Outdoor unit
Y branch
HR unit
Indoor unit
WARNING
* : Serial connection of HR units : Capacity sum of indoor units
160kBtu/hr
Refer to the HR unit PCB part for the valve group control setting.
It is recommended that difference in pipe lengths between an HR unit and indoor units, for example
difference in length of a, b, c, and d, be minimized. The larger difference in pipe lengths, the more different
performance between indoor units.
Piping length from outdoor branch to outdoor unit
10m(33ft), equivalent length : max 13m(43ft)
(For 18 HP or more)
If the large capacity indoor units(5~10 HP, using over
Ø
15.88(5/8) /
Ø
9.52(3/8))are installed, it
should use
Valve Group setting.
A1
C1
D1
D2
D3
D4
D6
D7
D8
D9
D10
E1
E2
A
C1
B
C2
C3
*
B1
B2
A2
a
b
c
d
e
g
j
k
f
i
H
h
"a"
"b"
F2
F1
D
E
C2
D5
C4
C3
Master
Slave 1
Case 1 ("a")
: Maximum height is 15m(236ft) if you install with Y branch.
Case 2 ("b")
: Height is zero(0) m in HR unit serial connector.