LG ARUB115BT2 Installation Manual - Page 33

Refrigerant pipe diameter between branches and HR units B,C,D, Total pipe length A+B+C1+C2+C3+D+a+b+

Page 33 highlights

ENGLISH Refrigerant piping installation ➲ Refrigerant pipe diameter between branches and HR units (B,C,D) Downward indoor unit total capacity [kW(Btu/h)] ≤ 5.6 (19,100) < 16.0 (54,600) < 22.4 (76,400) < 33 (112,600) < 47 (160,400) < 71 (242,300) < 104 (354,900) 104 (354,900) ≤ Liquid pipe [mm(inch)] Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4) Gas pipe [mm(inch)] Low pressure High pressure Ø12.7(1/2) Ø9.52(3/8) Ø15.88(5/8) Ø12.7(1/2) Ø19.05(3/4) Ø15.88(5/8) Ø22.2(7/8) Ø19.05(3/4) Ø28.58(1-1/8) Ø22.2(7/8) Ø28.58(1-1/8) Ø28.58(1-1/8) Ø34.9(1-3/8) Ø28.58(1-1/8) Ø41.3(1-5/8) Ø28.58(1 -1/8) ➲ Total pipe length (A+B+C1+C2+C3+D+a+b+c+d+e+f+g+i+j+k) ≤ 1000m(3280ft) E1 ~ D10 C3 ~ C4 B1 ~ D10 E1 ~ A3 H h g, I, j, k Outdoor unit ~ the farthest indoor unit Equivalent pipe length A+B+C3+D+K ≤ 150m(492ft)(200m(656ft))(*)) A+B+C3+D+K ≤ 175m(574ft)(225m(738ft))(*)) HR Unit ~ neighboring HR Unit D≤ 10m(33ft) First indoor branch ~ the farthest indoor unit B+C3+D+k ≤ 90m(295ft)(*) First outdoor branch ~ the farthest outdoor unit E+F3 ≤ 10m(33ft) Difference in height (outdoor unit ↔ indoor unit) H ≤ 100m(328ft) Difference in height (indoor ~ indoor unit) H ≤ 15m(49ft) Piping length from each indoor unit to the closest HR Unit a,b,c,d,e,f,g, i, j, k ≤ 40m(131ft) CAUTION • Assume equivalent pipe length of Y branch to be 0.5m(1.6ft), calculation purpose. CAUTION: • Should not be exceed 10m(33ft) between neighboring HR unit. • Serial connection of HR units : Capacity sum of indoor units ≤ 160kBtu/hr. Prohibited pattern Prohibited pattern HR1 1 2 3 4 48k 48k 48k 48k • Capacity sum of indoor units is over 160kBtu/hr. Pattern HR1 15m(49ft) HR2 1234 5678 12k 24k 24k 12k 48k 48k 48k 12k • Distance between neighboring HR unit is over 10m, and Capacity sum of indoor units is over 160kBtu/hr. Pattern A A HR1 HR2 HR1 HR2 1 2 3 36k 36k 36k 1 Indoor unit A Y Branch pipe Outdoor Unit Low pressure Gas pipe High pressure Gas pipe Liquid pipe HR Unit 4 36k Gas pipe Liquid pipe 1234 12k 24k 24k 12k Indoor Unit 5678 48k 48k 48k 12k Installation Manual 33

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83

Installation Manual
33
ENGLISH
Refrigerant piping installation
HR1
48k
48k
48k
48k
1
2
3
4
HR1
36k
36k
A
A
1
1
2
A
HR2
36k
36k
3
4
HR1
15m(49ft)
12k
12k
24k
24k
1
2
3
4
HR2
48k
48k
48k
12k
5
6
7
8
HR1
12k
12k
24k
24k
1
2
3
4
HR2
48k
48k
48k
12k
5
6
7
8
Prohibited pattern
Prohibited pattern
Pattern
Indoor unit
Capacity sum of indoor units is over 160kBtu/hr.
Distance between neighboring HR unit is over 10m,
and Capacity sum of indoor units is over 160kBtu/hr.
Y Branch pipe
Pattern
HR
Unit
Outdoor
Unit
Indoor
Unit
Low pressure Gas pipe
High pressure Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Refrigerant pipe diameter between branches and HR units (B,C,D)
Total pipe length (A+B+C1+C2+C3+D+a+b+c+d+e+f+g+i+j+k)
1000m(3280ft)
Downward indoor unit total capacity
[kW(Btu/h)]
5.6 (19,100)
Ø
6.35(1/4)
Ø
12.7(1/2)
Ø
9.52(3/8)
< 16.0 (54,600)
Ø
9.52(3/8)
Ø
15.88(5/8)
Ø
12.7(1/2)
< 22.4 (76,400)
Ø
9.52(3/8)
Ø
19.05(3/4)
Ø
15.88(5/8)
< 33 (112,600)
Ø
9.52(3/8)
Ø
22.2(7/8)
Ø
19.05(3/4)
< 47 (160,400)
Ø
12.7(1/2)
Ø
28.58(1-1/8)
Ø
22.2(7/8)
< 71 (242,300)
Ø
15.88(5/8)
Ø
28.58(1-1/8)
Ø
28.58(1-1/8)
< 104 (354,900)
Ø
19.05(3/4)
Ø
34.9(1-3/8)
Ø
28.58(1-1/8)
104 (354,900)
Ø
19.05(3/4)
Ø
41.3(1-5/8)
Ø
28.58(1 -1/8)
Liquid pipe
[mm(inch)]
Low pressure
High pressure
Gas pipe [mm(inch)]
Outdoor unit ~ the farthest indoor unit
Equivalent pipe length
A+B+C3+D+K
150m(492ft)(200m(656ft))(*))
A+B+C3+D+K
175m(574ft)(225m(738ft))(*))
HR Unit ~ neighboring HR Unit
D
10m(33ft)
First indoor branch ~ the farthest indoor
unit
B+C3+D+k
90m(295ft)(*)
First outdoor branch ~ the farthest outdoor unit
E+F3
10m(33ft)
Difference in height (outdoor unit
indoor unit)
H
100m(328ft)
Difference in height (indoor ~ indoor unit)
H
15m(49ft)
Piping length from each indoor unit to the closest HR Unit
a,b,c,d,e,f,g, i, j, k
40m(131ft)
E1
~
D10
C3
~
C4
B1
~
D10
E1
~
A3
H
h
g, I, j, k
CAUTION
Assume equivalent pipe
length of Y branch to be
0.5m(1.6ft), calculation
purpose.
CAUTION:
Should not be exceed
10m(33ft) between
neighboring HR unit.
Serial connection of
HR units : Capacity
sum of indoor units
160kBtu/hr.