Night silent operation Function
View all LG ARUB115BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 73 highlights
ENGLISH Night silent operation Function Test Run In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load. Max. RPM setting method Dip S/W No.12+14 ON Master ODU SW01B Note 1) Main PCB Power Reset Setting the Fan Max. RPM Master ODU SW01S SW01V SW02V Setting Complete Example of Max. RPM Setting Fan Max. RPM : Step 1 - Night silent operation start © 8 hours after max. ODU temp. sensing, the fan max. RPM is operated setting RPM. - Night silent operation end © 9 hours after Night silent operation is started, the function should be stopped automatically. CAUTION 1. Request installer to set the function during installation. 2. In case the function is not used, set the dip S/W OFF and reset the power. 3. If ODU RPM changes, cooling capacity may go down. [Note] 1. Select appropriate RPM referencing noise table. Setting Step Black button Red button Fan Max RPM Judgment (hr) Operation (hr) 1 1 time 1 time 510 8 9 2 2 times 1 time 510 6.5 10.5 3 3 times 1 time 510 5 12 4 4 times 1 time 450 8 9 5 5 times 1 time 450 6.5 10.5 6 6 times 1 time 450 5 12 7 7 times 1 time 400 8 9 8 8 times 1 time 400 6.5 10.5 9 9 times 1 time 400 5 12 Installation Manual 73