LG ARUB115BT2 Installation Manual - Page 36
Branch pipe Fitting
View all LG ARUB115BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Refrigerant piping installation Branch pipe Fitting Y branch A B A To Outdoor Unit B To Branch Piping or Indoor Unit • Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Horizontal plane Facing downwards Facing upwards Within +/- 10° A Viewed from point A in direction of arrow Within ± 3° Within ± 3° • There is no limitation on the joint mounting configuration. • If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter. • Branch pipe should be insulated with the insulator in each kit. Tape (field supply) Insulator (included with kit) Liquid and gas pipe joints Insulator for field piping 36 Outdoor Unit