LG ARUB115BT2 Installation Manual - Page 52
SW05M Rotary S/W for addressing HR unit, SW01M/SW03M/SW04M Dip S/W and tact S/W for manual valve
View all LG ARUB115BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 52 highlights
HR Unit PCB 2. SW05M (Rotary S/W for addressing HR unit) Must be set to '0' when installing only one HR unit. When installing multiple HR units, address the HR units with sequentially increasing numbers starting from '0'. Ex) Installation of 3 HR units 34 1234 34 1234 34 1234 3. SW01M/SW03M/SW04M (Dip S/W and tact S/W for manual valve addressing) - Used in manual addressing of the valve in the HR unit - Set the address of the valve of the HR unit to the central control address of the connected indoor unit. - SW01M: selection of the valve to address SW03M: increase in the digit of 10 of valve address SW04M: increase in the last digit of valve address - Prerequisite for manual valve addressing : central control address of each indoor unit must be preset differently at its wired remote control. S/W No. Setup No.1 Manual addressing of valve #1 No.2 Manual addressing of valve #2 SW01M No.3 No.4 Manual addressing of valve #3 Manual addressing of valve #4 SW03M SW03M Increase in the digit of 10 of valve address SW04M SW04M Increase in the last digit of valve address 52 Outdoor Unit